Customize the controllable outlet groups and the UPS outlets
Use the Control menus to change the controllable outlet groups and the UPS outlet settings.
Function | Factory Default | Options | Description | |
|
|
|
| |
Name String Outlet | Outlet Group 1 | Edit these names using an external interface, such as the Network | ||
Group | ||||
|
| Management Card Web interface. | ||
UPS Name String | UPS Outlets | |||
|
| |||
|
|
|
| |
Turn On Delay |
| Set the value in | The amount of time the UPS or Controllable Outlet | |
0 sec | Group will wait between receiving the command to | |||
seconds | ||||
|
| turn on and the actual startup. | ||
|
|
| ||
|
|
|
| |
Turn Off Delay |
| Set the value in | The amount of time that the UPS or Controllable | |
0 sec | Outlet Group will wait between receiving the | |||
seconds | ||||
|
| command to turn off and the actual shut down. | ||
|
|
| ||
|
|
|
| |
Reboot Duration | 4 sec | Set the value in | The amount of time that the UPS or Controllable | |
seconds | Outlet Group must remain off before it will restart. | |||
|
| |||
|
|
|
| |
Minimum |
| Set the value in | The amount of battery runtime that must be available | |
0 sec | before the UPS or Controllable Outlet Group will | |||
Return Time | seconds | |||
| turn on. | |||
|
|
| ||
|
|
|
| |
|
| • Shutdown with | When the unit switches to battery power, the UPS | |
|
| Delay | can disconnect power to the Controllable Outlet | |
|
| • Shutdown | Groups to save runtime. | |
Load Shed | Disabled | immediately |
| |
On Battery | • Turn off | Configure this delay time, use the LOAD SHED TIME | ||
|
| immediately | WHEN ON BATTERY setting. | |
|
| • Turn off with delay |
| |
|
| • Disabled |
| |
|
|
|
| |
Load Shed Time when | Disabled | Set the value in | The amount of time the outlets will function on | |
On Battery |
| seconds | battery power before they will turn off. | |
|
| • Shutdown with |
| |
|
| delay | When the battery runtime falls below the specified | |
|
| • Shutdown | ||
|
| value, the Controllable Outlet Group will turn off. | ||
Load Shed On | Disabled | immediately | ||
| ||||
Runtime | • Turn off | Configure this time using the LOAD SHED RUNTIME | ||
| ||||
|
| immediately | ||
|
| REMAINING setting. | ||
|
| • Turn off with delay | ||
|
| • Disabled |
| |
|
|
|
| |
Load Shed On | Disabled | Set the value in | When the remaining runtime reaches this level, the | |
Runtime Remaining | seconds | Controllable Outlet Group will turn off. | ||
| ||||
|
|
|
| |
|
| • Disabled | In the event of an overload (greater than 100% | |
Load Shed on |
| • Enabled | output), the Controllable Outlet Group will | |
Disabled |
| immediately turn off to conserve power for critical | ||
Overload |
| |||
|
| loads. The Controllable Outlet Group will only turn | ||
|
|
|
on again with a manual command.
11 |