APC SMX48RMBP2U, SMX750 VA, SMX 1500 VA Using the controllable outlet groups and UPS outlets

Page 12

Using the controllable outlet groups and UPS outlets

The UPS outlets function as a master switch. They turn on first when power is applied, shut off last when there is a power outage and battery runtime has been exhausted.

The UPS outlets must be turned on for the Controllable Outlet Groups to turn on.

1.Connect critical equipment to the UPS outlets (The 1500 VA units do not have UPS outlets. Connect all critical equipment to the same outlet group.)

2.Connect peripheral equipment to the Controllable Outlet Groups.

Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery runtime can be added to a short power off delay

If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups

Equipment that needs to reboot independently from other equipment should be added to a separate group

3.Use the Configuration menus to configure how the Controllable Outlet Groups will react in the event of a power outage.

10

Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U

Image 12
Contents Smart-UPS X Uninterruptible Power Supply Page Important Safety Messages Safety and General InformationProduct Description Front Panel Features Rear Panel FeaturesProduct Overview 120 VacSpecifications InstallationEnvironmental Specifications Network Management Card External Battery PackBasic Connectors OperationConnect Equipment to the UPS Using the display interface Display PanelOverview Standard menusAdvanced menus ControlLog Configuration UPS SettingsStart up settings General SettingsControllable Outlet Groups Model specific controllable outlet groups 750 VA 120 Vac1000 VA 120/230 Vac 1500 VA 120/230 VacUsing the controllable outlet groups and UPS outlets Turn On Delay Turn Off DelayReboot Duration On BatteryNetwork Management Card Settings Emergency Power Off Normally open contactsNormally closed contacts Troubleshooting UPS does not provide expected backup timeUPS is emits intermittent beeps Display interface LEDs flash sequentiallyReplace Battery LED is illuminated UPS displays a site wiring fault messageService Transport the unitTwo Year Limited Factory Warranty Non-transferable warrantyPage APC by Schneider Electric Worldwide Customer Support 990-3458B 04/2013