APC SMX48RMBP2U, SMX750 VA, SMX 1500 VA Troubleshooting, UPS is emits intermittent beeps

Page 16

Troubleshooting

Problem and Possible Cause

Solution

 

The UPS will not turn on or there is no output

 

 

The unit has not been turned on.

Press the ON button once to turn on the UPS.

 

 

The UPS is not connected to utility

Be sure that the power cable is securely connected to the unit and to the utility

power.

power supply.

 

 

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the

circuit breaker.

 

 

 

The unit shows very low or no input

Check the utility power supply to the UPS by plugging in a table lamp. If the

utility voltage.

light is very dim, check the utility voltage.

 

 

The battery connector plug is not

Be sure that all battery connections are secure.

securely connected.

 

 

 

There is an internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced

immediately.

 

 

The UPS is operating on battery, while connected to utility power

 

 

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the

circuit breaker.

 

 

 

There is very high, very low, or

Move the UPS to a different outlet on a different circuit. Test the input voltage

with the utility voltage display. If acceptable to the connected equipment,

distorted input line voltage.

reduce the UPS sensitivity.

 

 

 

UPS is emits intermittent beeps

 

 

 

The UPS is in normal operation.

None. The UPS is protecting the connected equipment.

 

UPS does not provide expected backup time

 

 

 

Charge the battery. Batteries require recharging after extended outages and

The UPS battery is weak due to a

wear out faster when put into service often or when operated at elevated

recent outage or is near the end

temperatures. If the battery is near the end of its service life, consider

of its service life.

replacing the battery even if the replace battery indicator is not yet

 

illuminated.

 

 

The UPS is overloaded.

Check the UPS load display. Unplug unnecessary equipment, such as printers.

 

Display interface LEDs flash sequentially

 

 

The UPS has been shut down remotely

None. The UPS will restart automatically when utility power is restored.

through software or an optional accessory

 

card.

 

The Site Wiring Fault LED illuminates

The UPS displays a fault message and emits a constant beeping sound

Internal UPS fault.

Do not attempt to use the UPS. Turn the UPS off and have it serviced

immediately.

 

14

Smart-UPS X 750/1000/1500 VA 120/230 Vac Rack-Mount 2U

Image 16
Contents Smart-UPS X Uninterruptible Power Supply Page Safety and General Information Important Safety MessagesProduct Description Front Panel Features Rear Panel FeaturesProduct Overview 120 VacSpecifications InstallationEnvironmental Specifications Network Management Card External Battery PackOperation Basic ConnectorsConnect Equipment to the UPS Using the display interface Display PanelOverview Standard menusControl Advanced menusLog Configuration UPS SettingsStart up settings General SettingsControllable Outlet Groups Model specific controllable outlet groups 750 VA 120 Vac1000 VA 120/230 Vac 1500 VA 120/230 VacUsing the controllable outlet groups and UPS outlets Turn On Delay Turn Off DelayReboot Duration On BatteryNetwork Management Card Settings Normally open contacts Emergency Power OffNormally closed contacts Troubleshooting UPS does not provide expected backup timeUPS is emits intermittent beeps Display interface LEDs flash sequentiallyReplace Battery LED is illuminated UPS displays a site wiring fault messageService Transport the unitTwo Year Limited Factory Warranty Non-transferable warrantyPage APC by Schneider Electric Worldwide Customer Support 990-3458B 04/2013