American Power Conversion 10-40kW System OFF Normal operation Load power 0% Bypass operation

Page 11

Stop/Start UPS and Operating the External Service Bypass

Action

1.Set the input switch (Q001) to position 1

2.Wait 5 sec. Open the front door of the UPS and press the green ON key

3.Press on the keyboard

4.

Press

or

on the keyboard until

5.

Press

on the keyboard

6.Press on the keyboard

7.Check light indication on the bypass panel

8.Set the output switch (Q002) to position 1

9.Set the bypass switch (Q003) to position 0

10.Press on the keyboard

11.Press or on the keyboard until

12. Press

on the keyboard

13.Press on the keyboard

14.Press on the keyboard

15. Press

on the keyboard

Display shows

**System OFF**

Normal operation

load power 0%

Bypass operation

: NO

Bypass operation

: YES

Lamp indication on Bypass Panel

Green light (H002) above the output switch handle (Q002) lights up

Green light (H003) above the bypass switch handle (Q003) lights up

Only the light (H003) above the bypass switch handle (Q003) is now on

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

All lights on the bypass panel switched off

NOTICE!

If battery has been disconnected, please refer to section 2.4.1 UPS start-up.

 

990-4043

 

 

User Guide APC Silcon 10-40kW 400V UPS

11

Image 11
Contents Copyright 2000 APC Denmark ApS 10-40kW 400V UPS User GuideThank You Safety Symbols used in this manualUser Guide APC Silcon 10-40kW 400V UPS Contents Display Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassNormal operation Load power xx% Stop UPS for stand-byBlank Stop UPS for complete power downSwitching off the UPS UPS start-up Start UPS from complete power downDisplay shows Bypass operation Operating the External Service Bypass Switch single systemsBypassing the Single System UPS Stop/Start UPS and Operating the External Service Bypass Bypass operation Normal operation Load power 0% System OFF Normal operation Load power 0% Bypass operationBypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Press On the keyboard Set input switches Q001 to positionPress the green on button on all systems Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Batt. load Batt. tank Using the Remote DisplayDisplay of Measured Values Economy Mode Parameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsDisplay will show invalid UPS data Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestTest Press Battery capacity TestUntil Test Xxx PressAPC Silcon UPS Limited Factory Warranty WarrantyWarranty APC Denmark How to Contact APCHow to Contact APC APC Corporate