American Power Conversion 10-40kW Operating the External Service Bypass Switch single systems

Page 9

Stop/Start UPS and Operating the External Service Bypass

2.5Operating the External Service Bypass Switch (single systems)

2.5.1 Bypassing the Single System UPS

Mains

Load

Service Bypass

Switch

APC Silcon

UPS

Action

 

 

1.

Press

on the keyboard

2.

Press

or

on the keyboard until

3.

Press

on the keyboard

4.

Press

on the keyboard

5.Check light indication on the bypass panel

6.Set the external bypass switch (Q003) to position 1

7.Set the output switch (Q002) to position 0

8.Open the front door and press the green ON and the red OFF button simultaneously

The acoustic alarm sounds for 30 seconds*

9.Set the input switch (Q001) to position 0

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 seconds*

*Use the key to reset the acoustic alarm

Display shows

Bypass operation

: NO

Bypass operation

: YES

Lamp indication on Bypass Panel

Green light (H003) above the bypass switch handle (Q003) lights up

Green light (H002) above the output switch handle (Q002) lights up

Only the light (H002) above the output switch handle (Q002) is now on

Display shows

**System OFF**

 

990-4043

 

 

User Guide APC Silcon 10-40kW 400V UPS

9

Image 9
Contents Copyright 2000 APC Denmark ApS 10-40kW 400V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 10-40kW 400V UPSThank You Contents Introduction IntroductionDisplay Unit Normal operation Load power xx% Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Start UPS from stand-byStop UPS for complete power down Switching off the UPSBlank UPS start-up Start UPS from complete power downDisplay shows Operating the External Service Bypass Switch single systems Bypassing the Single System UPSBypass operation Stop/Start UPS and Operating the External Service Bypass Bypass operation Normal operation Load power 0% System OFF Normal operation Load power 0% Bypass operationBypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Press the green on button on all systemsPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsAlarms Description Action Possible AlarmsDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Battery capacity TestTest Xxx Press Test PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark