American Power Conversion 10-40kW Set input switches Q001 to position, Press On the keyboard

Page 15

Stop/Start UPS and Operating the External Service Bypass

Action

Display shows

 

1.Check that the output switch (Q004) is set to position 0

2.Check that all output switches (Q002) are set to position 1

3. Set input switches (Q001) to position 1

**System OFF**

4.Wait 10 secs.

Open the UPS front door and

press the green ON button on all systems

Normal operation

load power 0%

 

 

5. Press

on the keyboard

 

6.

Press

or

on the keyboard until

7.

Press

on the keyboard

8.Press on the keyboard

All systems switch to bypass operation

Note!

If Q002s are in position 0 off, only programmed systems will switch to bypass

9.Set the output switch (Q004) to position 1

10.Turn the bypass switch (Q003) to position 0

The following can be carried out on any UPS

11. Press

on the keyboard

12. Press

or

on the keyboard until

13. Press

on the keyboard

14. Press

on the keyboard

All the systems will transfer to normal operation

Bypass operation

: NO

Bypass operation

: YES

Bypass operation

Lamp indication on Bypass Panel

H002 and H004 light up

Green light (H003) above bypass switch lights up

The green lamps (H002) and (H004) are switched off, but (H003) is lit until normal operation.

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

No lamps on the bypass panel are lit

 

990-4043

 

 

User Guide APC Silcon 10-40kW 400V UPS

15

Image 15
Contents Copyright 2000 APC Denmark ApS 10-40kW 400V UPS User GuideSafety Symbols used in this manual User Guide APC Silcon 10-40kW 400V UPSThank You Contents Introduction IntroductionDisplay Unit Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassNormal operation Load power xx% Stop UPS for stand-byStop UPS for complete power down Switching off the UPSBlank UPS start-up Start UPS from complete power downDisplay shows Operating the External Service Bypass Switch single systems Bypassing the Single System UPSBypass operation Stop/Start UPS and Operating the External Service Bypass Bypass operation Normal operation Load power 0% System OFF Normal operation Load power 0% Bypass operationBypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Press the green on button on all systemsPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Mode Comments Alarms and EventsAlarms and Events Displaying the Alarm StackAlarms Description Action Possible AlarmsDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Battery Capacity Test Maintenance & TestingMaintenance & Testing Battery Monitoring TestTest Press Battery capacity TestUntil Test Xxx PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty APC Denmark How to Contact APCHow to Contact APC APC Corporate