Toshiba T2 Series user manual Parity Check, Pen Evn, None OFF ODD Even, ASY and DLY switches

Page 17

Parity Check:

Select the parity check as odd, even or none. Use switches 7 and 8 to set the parity.

PARITY

PEN (7)

EVN (8)

 

 

 

NONE

OFF

----

 

 

 

ODD

ON

OFF

 

 

 

EVEN

ON

ON

 

 

 

ASY and DLY switches:

The ASY and DLY switches are not used on the EX10-MML11, and should be set to the “Off” position.

Page 11

Image 17
Contents Prosec T2-Series Important Information Hazard Classifications Safety PrecautionsAbout This Guide Contents Page Overview Modbus Module System ConfigurationTo 1 Configuration To N Configuration External Features and Switch Settings Specifications Modbus Function Code T2 Command Modbus Module Operation Modbus CommandsReg/Device Address T2 Modbus Data Types and T2 Register MappingData Type Attribute Modbus No Offset Modbus T2 Address mapping Example Restricted RegistersStation Number Modbus Module SetupModbus Module DIP Switch Settings Reserved BR2 BR1 BR0Parity Check ASY and DLY switchesParity PEN EVNExample Configuration Settings ASY DLY Had BR2 BR1 BR0 PEN EVN Wiring Connection to the Modbus Module CPU Setup for the Modbus Module If the LED indicators are on solid Trouble ShootingIf the LED indicators are not flashing, check the following Additional References Toshiba do BRASIL, S.A Toshiba International Corporation Toshiba Corporation