Toshiba T2 Series Trouble Shooting, If the LED indicators are not flashing, check the following

Page 22

8. Trouble Shooting

The communication status LEDs can be used to verify correct operation of the Modbus module. During normal operation, the LED indicators flash as follows:

RXD LED: Flashes when the Modbus master sends a message to the EX10

-MML11. On a multi slave network, this can also flash when when the master polls other slaves, or when other slaves respond to the master. In general, it indicates activity on the network.

TXD LED: Flashes when that specific EX10-MML11 responds to the master.

This LED is only relevant to the module on which it is being viewed, regardless of how many slaves are on the network. It indicates that the module has received a message that is uniquely addressed to it, and the EX10-MML11 is responding. This LED is usually on longer than the RXD LED because the responses have more data than the requests.

If the LED indicators are not flashing, check the following:

1)Wiring connections

2)Resistance at terminals

3)Baud rate setting

4)Station Number

5)HAD Switch

6)Parity selection

7)Modbus master is using standard Modbus RTU format

If the LED indicators are on solid:

The polarity has been reversed on the network wiring. For example, the “A” terminals are wired to the “B” lines, the “+” terminals are wired to the “-“ lines, etc. Correct the connections to the EX10-MML11.

Page 16

Image 22
Contents Prosec T2-Series Important Information Safety Precautions Hazard ClassificationsAbout This Guide Contents Page Overview To 1 Configuration System ConfigurationModbus Module To N Configuration External Features and Switch Settings Specifications Modbus Module Operation Modbus Commands Modbus Function Code T2 CommandData Type Attribute Modbus No Offset Modbus Data Types and T2 Register MappingReg/Device Address T2 Restricted Registers Modbus T2 Address mapping ExampleModbus Module DIP Switch Settings Modbus Module SetupStation Number BR2 BR1 BR0 ReservedParity ASY and DLY switchesParity Check PEN EVNExample Configuration Settings ASY DLY Had BR2 BR1 BR0 PEN EVN Wiring Connection to the Modbus Module CPU Setup for the Modbus Module If the LED indicators are not flashing, check the following Trouble ShootingIf the LED indicators are on solid Additional References Toshiba International Corporation Toshiba Corporation Toshiba do BRASIL, S.A