5.Modbus Module Operation

5.1.Modbus Commands

When a MODBUS command is used, the Modbus module translates it to the corresponding T2 register access protocol.

 

MODBUS FUNCTION CODE

 

T2 COMMAND

 

 

 

 

01

Read Coil Status

DR

Read Device/Register

02

Read Input Status

DR

Read Device/Register

03

Read Holding Register

DR

Read Device/Register

04

Read Input Register

DR

Read Device/register

05

Force Single Coil

DW

Write Device Register

06

Force Single Register

DW

Write Device/Register

08

Loop Back Diagnostic test

**** Not Supported by EX10-MML11

15

Force Multiple Coils

DW

Write Device/register

16

Preset Multiple Registers

DW

Write Device/register

For more information on the Modbus protocol, please refer to the Modbus Protocol Reference Guide, see Additional References.

For more information on the T2 register access protocol, please refer to the Computer Link Function Operation Manual, see Additional References.

Page 6

Image 12
Contents Prosec T2-Series Important Information Safety Precautions Hazard ClassificationsAbout This Guide Contents Page Overview System Configuration To 1 ConfigurationModbus Module To N Configuration External Features and Switch Settings Specifications Modbus Module Operation Modbus Commands Modbus Function Code T2 CommandModbus Data Types and T2 Register Mapping Data Type Attribute Modbus No OffsetReg/Device Address T2 Restricted Registers Modbus T2 Address mapping ExampleModbus Module Setup Modbus Module DIP Switch SettingsStation Number BR2 BR1 BR0 ReservedASY and DLY switches Parity CheckParity PEN EVNExample Configuration Settings ASY DLY Had BR2 BR1 BR0 PEN EVN Wiring Connection to the Modbus Module CPU Setup for the Modbus Module Trouble Shooting If the LED indicators are not flashing, check the followingIf the LED indicators are on solid Additional References Toshiba International Corporation Toshiba Corporation Toshiba do BRASIL, S.A