Toshiba RBC-FDP2-F-PE specifications Advanced control

Page 2

FDP2 Advanced Operation

 

 

FDP2 Group Control

FDP2 Duty/Standby Operation

 

ADDRESSING

 

 

 

Group control allows up to 16 FDP2s to be connected on a D-Bus local

Duty/Standby will alternately run two systems on 24 hour

SW3 ON for

The FDP2 has the facility to create control groups using multiple FDP2s

network. Each FDP2 reports faults for the locally attached units. The

alternating run/standby. If a fault occurs on either system

Duty/standby

connected together on the D-Bus network. In standard configuration up

FDP2 with address 0 is a MASTER and determines the settings for all

then both systems are switched on until the fault is

 

to 16 FDP2 devices can be connected together. Each FDP2 is assigned

systems connected to FDP2s addressed as slaves. The operating mode

cleared.

 

a D-Bus address using the configuration switches SW4 to SW7. Unit

of the master is determined by SW1, SW2 as shown in the Standard

Duty/Standby is achieved using two FDP2 devices, one with Address 0

addresses are shown below.

 

 

Operation configuration instructions overleaf.

 

 

and one with Address 1 with a D-BUS connection between the two. SW3

ADDRESS 0

ADDRESS 4

ADDRESS 8

ADDRESS 12

 

LOCAL CONTROL

must be switched ON on both devices to enable the operation.

 

 

 

 

 

 

 

 

 

 

With SW1 OFF and SW2 OFF the MASTER FDP2 system operates under

21

 

 

 

 

 

the control of the attached remote controller. SLAVE FDP2 devices will

 

ADDRESS 1

ADDRESS 5

ADDRESS 9

ADDRESS 13

 

 

duplicate these settings to allow large groups to be controlled from one

 

8 Units max

 

 

 

 

 

 

 

 

 

 

remote controller. Remote controllers on the slave FDP2s are locked and

 

 

 

 

 

 

can be omitted if desired.

 

 

ADDRESS 2

ADDRESS 6

ADDRESS 10

ADDRESS 14

 

 

 

8 Units max

ADDRESS 3 ADDRESS 7 ADDRESS 11 ADDRESS 15

 

 

Address 0 (MASTER)

 

DUTY/STANDBY 1 Day 1 Day 1 Day FAULT

Address 0 is the FDP2 MASTER address. Address 1 to 15 are FDP2

 

SLAVE addresses that can be used to create large control groups.

21

8 Units max

NETWORK INSTALLATION

Address 0 (MASTER)

 

The D-Bus network requires a twisted pair cable connecting terminals

 

 

D1 and D2 on each FDP2 as shown below. Terminal D1 must be

 

 

connected to all other D1 terminals. Terminal D2 must be connected to

 

 

all other D2 terminals. In addition the common terminal C on all devices

 

 

must be connected together. If a shielded cable is used then the shield

8 Units max

 

 

 

can be used for this purpose. The network must be installed as a point

D-BUS

Address 1 (SLAVE)

to point BUS configuration, Star and Ring connections must NOT be

16 FDP2 max

 

used.

 

 

 

 

 

 

 

 

 

 

 

The MASTER FDP2 can be configured using SW1 and SW2 to operate

 

 

 

 

 

 

 

 

 

using one of the three preset modes Heat, Cool or Auto. Alternatively the

 

 

 

 

 

 

D-BUS

Address 1 (SLAVE)

 

MASTER can be configured for local control, in which case the remote

 

 

 

 

 

 

 

controller attached to the MASTER FDP2 can be used to set the operating

 

 

 

 

 

 

16 FDP2 max

 

 

 

 

 

 

 

 

 

ADDRESS 0

ADDRESS 1

 

 

 

settings during master duty.

 

 

PRESET CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Advanced control

 

 

 

 

 

 

 

 

If the master is configured for Heat, Cool or Auto preset control then the

 

 

 

 

 

 

 

 

More sophisticated control con be achieved using the FDP2-BMS

 

 

 

 

 

 

FDP2 slave units will operate to the same settings as the master. The

 

 

 

 

 

 

interface, this provides a number of inputs that allow external control of

TCC-NET

D-BUS

RELAY

TCC-NET

D-BUS

RELAY

diagram below shows the system configured for

the Cool preset. See

A B

D1 D2

C R1 R2

A B

D1 D2

C R1 R2

unit operation, or connection to Building Management Systems. The

 

 

 

 

 

 

overleaf for SW1, SW2 settings for Heat and Auto presets.

 

 

 

 

 

 

FDP2 interfaces can also be customised for specific operating

 

 

 

 

 

 

 

 

 

 

 

D1

D1

 

 

18

 

 

requirements. Contact Toshiba for details.

 

 

 

 

 

 

 

 

 

 

 

 

 

D2

D2

 

 

 

 

8 Units max

 

 

 

 

 

 

C

C

 

 

 

 

 

Functional Specification

 

 

 

 

 

 

 

 

 

 

 

 

 

SPECIFICATION

 

 

 

 

 

 

 

Electrical

 

Environmental

 

Use solid or stranded 24awg shielded or unshielded twisted pair to

 

 

 

 

 

 

 

 

Supply

18V DC from TCC-NET

Temperature

 

Cat3, Cat4 or Cat5 specification. Use a twisted pair for connections

 

 

 

 

 

 

 

 

 

Storage

-10oC to 50oC

D1,D2 and an extra core for connection C.

 

 

 

 

 

 

 

 

 

 

 

 

Power

<1VA

Operation

0oC to 50oC

 

 

 

 

 

 

 

Address 0 (MASTER)

 

 

 

 

 

NETWORK LENGTH

 

 

 

 

 

 

Relay

1A, 24VAC max

Humidity

0-90% RH

Standard installation for total network distances of up to 500m can be

 

 

 

 

1A, 30VDC max

 

non-condensing

 

 

 

 

 

 

 

achieved following the basic daisy-chaining method showed in the

18

 

 

Mechanical

 

Protection

IP30

above diagram. Network layout should follow a point-to-point

 

 

Dimensions

H72 x W87 x D19

 

 

 

 

 

EMC Emissions

EN61000-6-1

connection, ‘T’ and star connections are not supported,

 

 

 

8 Units max

(mm)

 

 

 

 

 

 

 

 

 

 

Mounting

Two keyhole mounting

EMC Immunity

EN61000-6-3

 

 

 

 

 

 

 

 

 

 

flanges

 

 

 

 

 

 

 

 

 

 

 

Casing

Zinc coated mild steel

 

 

 

 

 

 

 

 

 

 

 

Weight

80g

 

 

 

 

 

 

 

 

D-BUS

 

 

Connectors

Rising clamp to 0.75mm2

 

 

 

 

 

 

 

 

Address 1 (SLAVE)

 

 

cable

 

 

 

 

 

 

 

 

16 FDP2 max

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9570-0 FDP2-F Installation & Operating Instructions issue 1.14.02

Copyright © RealTime Control Systems Limited. 2005

Image 2
Contents Mounting Basic Cable InstallationFault Reporting Standard OperationAdvanced control