Siemens 480V manual Weights and Dimensions, Breaker Element Weight in lbs. kg

Page 15

480V Metal-Enclosed Switchgear

Weights and Dimensions

Dimensions

Siemens 480 volt switchgear can be configured in many ways by combining different section types. Up to five vertical sections plus a transition section can be shipped together as a unit. If all vertical sections are not to be shipped as a unit, specifications need to be provided that describe the limiting factors (e.g., low door or narrow hallway).

Normal indoor vertical sections are 101 in. (2565 mm) high and 60 in. (1524 mm) deep. A top-mounted hoist, which is shipped as an accessory in a separate container, adds 2 in. (51 mm) for a total installed height of 103 in. (2616 mm).

The outdoor switchgear assembly contains the indoor assembly in an out- door housing. The overall height is 113 in. (2870 mm) and the depth is 119.40 in. (3033 mm).

The major assembly sections include:

JTransition Sections — used as transi- tion to liquid filled transformer or to outdoor dry type transformers.

JAuxiliary Sections — used as incom- ing bus duct or cable entrance when a main breaker is not used.

JMain Sections — used to contain main breaker and may house metering and feeder breakers.

JFeeder Sections — used to contain feeder breakers and other equipment such as instrumentation.

JTie Sections — used to contain tie breaker and other equipment such as feeder breakers.

Transition Section For Liquid Filled and Outdoor Dry Type Transformers

Table 4.18

 

Dimension A

Weight

 

in Inches (mm)

in lbs. (kg)

Outdoor

55 (1397)

500 (227)

Indoor

61 (1549)

550 (250)

Table 4.19 Breaker Element Weight in lbs. (kg)

 

Element Type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

RL-800

RLE-800

RLI-800

RL-1600

RLE-1600

RL-2000

RLE-2000

RL-3200

RLE-3200

RL-4000

RLE-4000

RL-5000

Manual

140

(64)

170

(64)

175

(80)

180

(82)

185

(84)

210

(95)

215

(98)

290

(132)

295

(134)

350

(159)

355

(161)

425

(193)

Electrical

150

(68)

180

(82)

185

(84)

190

(86)

195

(89)

220

(100)

225

(102)

300

(136)

305

(139)

360

(164)

365

(166)

445

(202)

Additional

45

(20)

45

(20)

45

(20)

45

(20)

45

(20)

45

(20)

45

(20)

50

(23)

50

(23)

50

(23)

50

(23)

55

(25)

Weight for

Shipping

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 4.20 Fused Element Weight in lbs. (kg)

 

Element Type

 

 

 

 

 

 

 

 

 

Operation

RLF-800

RLF-1600

RLF-2000

RLF-3200

RFC-3200a

RLF-4000

RFC-4000b

RLF-5000

RFC-5000d

Manual

195

(89)

310

(141)

325

(148)

290c (132)

390c

350c (95)

450c

425c (193)

475 (217)c

Electrical

205

(93)

320

(145)

335

(152)

330c (150)

(177)

360c (100)

(205)

445c (202)

 

Additional

45

(20)

45

(20)

45

(20)

50 (23)

50 (23)

45 (20)

50 (23)

55 (25)

55 (25)

Weight for

Shipping

 

 

 

 

 

 

 

 

 

 

 

 

aFor use with RLF-3200 breaker. b For use with RLF-4000 breaker.

c Fuses mounted on separate drawout carriage and located in separate compartment. For total weight, add weight of breaker element and separate fuse carriage.

d For use with RLF-5000 breaker.

4

480V Metal Switchgear- Enclosed

CSI Section 16470

Siemens Electrical Products and Systems

63

 

Specification Guide

 

Image 15
Contents Industry Standards LV switchgear is typically installedGeneral Utility and Co-generation Facilities480V Metal-Enclosed Switchgear Finish Assembly ConstructionConstruction Details GeneralCircuit Breaker Compartments Control WiringMain and Ground Bus InsulationOptions Guide Form SpecificationsPrimary Disconnects LV Power Circuit BreakersTypical Breaker Features Circuit Breaker RackingCurrent Limiting Fuses Ground ConnectionDrawout Interlocks Arc InterruptionLV Power Circuit Breaker Trip Unit Static Trip III SettingsStatic Trip III Trip Unit Tripping Actuator Shunt Trip Coil Ratings Accessories/ModificationsRL Breaker Static Trip Iiicpx Protective Relay FunctionsRL Breaker Accessories / Modifications cont’d 11 Control Power Transformers-115C Rise VT, CPT, CT DataTechnical LV Power Circuit Breakers Ratings 15 Type RLF Fused Circuit Breaker Ratings At 50/60 Hertz 16 Type RL Circuit Breaker Operating Data 60 Hertz Basis17 Type RL Circuit Breaker Control Data Time/Current Characteristics of Static Trip III Trip Unit 20 Fused Element Weight in lbs. kg Weights and DimensionsDimensions 19 Breaker Element Weight in lbs. kgTie Breaker Sections and Combinations Front Views Auxiliary / Breaker Section Dimensions22 Breaker Section and Connection Weights in lbs. kga Breaker DesignationsIndoor Floor Plan, Side View Indoor Floor PlanIndoor Side View Outdoor Floor Plan Outdoor Floor Plan, Side ViewBus SpecificationsAssembly Codes and StandardsInstrumentation and Metering TestingCircuit Breakers Solid State Trip Units