480V Metal-Enclosed Switchgear
Construction Details
General
4
Main and Ground Bus
The standard main bus is
The main
Main bus ratings available are 1600, 2000, 3200, 4000, or 5000 amperes con- tinuous current. A neutral bus is fur- nished when specified, and can be rated 1600, 2000, 3200, 4000 or 5000 amperes continuous current.
A standard copper ground bus extends through all sections. A cable lug can be mounted to the ground bus in each section.
Minimum bus bracing is 65,000 amperes RMS symmetrical. Higher symmetrical bracings are available based on the low- est breaker short circuit rating in the group.
Load side runbacks for feeder circuits are
Control Wiring
Standard secondary and control wiring is #14 AWG
For devices not having
Insulation
The insulation used is
Circuit Breaker Compartments
Typical circuit breaker compartments include primary disconnects, ground dis- connect, drawout rails, and associated interlocks, and secondary disconnects, if appropriate. Telescoping drawout rails allow the breaker to be withdrawn from the compartment without additional extensions or adapters. Compartments for
Circuit breaker compartment front panels can be used to hold a variety of auxiliary devices such as breaker control switch- es, ammeters, and test blocks.
480V
a | Control Circuit Fuses |
| f | TOC Switch Operator |
b | Ground Disconnect |
| g | Interference Interlock |
c | Secondary Disconnect |
| h | MOC Switch Operator |
d | Front Panel Devices |
| i | Space Heater |
e | Primary Disconnect |
| j | Drawout Rails |
|
|
|
|
|
Circuit Breaker Cell Interior
52 | Siemens Electrical Products and Systems | CSI Section 16470 | |
Specification Guide | |||
|
|