Siemens 480V manual VT, CPT, CT Data, Technical, Control Power Transformers-115C Rise

Page 11

480V Metal-Enclosed Switchgear

VT, CPT, CT Data

Technical

Table 4.10

Voltage Transformers

 

 

 

 

 

 

Accuracy Class at 60 Hz

 

 

 

Thermal

 

 

Burden

 

 

 

 

 

 

 

Volt-Amp

Rating

 

Ratio

W

X

Y

Hertz

Rating

VA

600:120

0.6

0.6

1.2

100

150

50/60

480:120

0.6

0.6

1.2

100

150

50/60

288:120

0.6

0.6

1.2

100

150

50/60

 

 

 

 

 

 

 

Table 4.11 Control Power Transformers—115°C Rise

kVA

Phase

Primary

Secondary

Voltage

Voltage

3

 

 

 

5

Single

240/480

120/240

10 a

15 a

 

 

 

aRequires complete compartment.

Table 4.12 Current Transformers for RL-800, RLE-800, RLI-800, RL-1600, RLE-1600, RL-2000, or RLE-2000 Applicationsb

 

Accuracy at 60 Hz Metering Burden (ohms)

 

 

 

Relay

Ratio

B-0.1

B-0.2

 

B-0.5

B-1.0

B-2.0

Class

100:5

1.2

2.4

 

C5

150:5

1.2

2.4

 

C5

200:5

1.2

1.2

 

C10

250:5

0.6

1.2

 

C10

300:5

0.6

0.6

 

1.2

C10

400:5

0.6

0.6

 

1.2

C5

500:5

0.6

0.6

 

0.6

C10

600:5

0.3

0.6

 

0.6

1.2

C10

800:5

0.3

0.3

 

0.6

0.6

C15

1000:5

0.3

0.3

 

0.3

0.6

1.2

C20

1200:5

0.3

0.3

 

0.3

0.6

1.2

C20

1500:5

0.3

0.3

 

0.3

0.3

0.6

C30

1600:5

0.3

0.3

 

0.3

0.3

0.6

C30

2000:5

0.3

0.3

 

0.3

0.3

0.6

C5

2500:5

0.3

0.3

 

0.3

0.3

0.3

C10

bBreaker compartment will accept 3 CT’s in-line on lower disconnects.

Table 4.13 Current Transformers for RL-3200c, RLE-3200c, RL-4000d, RLE-4000d, or RL-5000bApplications

 

Accuracy at 60 Hz Metering Burden (ohms)

 

 

 

Relay

Ratio

B-0.1

B-0.2

 

B-0.5

B-1.0

B-2.0

Class

1000:5

0.3

0.3

 

0.6

0.6

1.2

C20

1200:5

0.3

0.3

 

0.3

0.6

1.2

C25

1500:5

0.3

0.3

 

0.3

0.3

0.6

C35

2000:5

0.3

0.3

 

0.3

0.3

0.3

C25

2500:5

0.3

0.3

 

0.3

0.3

0.3

C30

3000:5

0.3

0.3

 

0.3

0.3

0.3

C15

3200:5

0.3

0.3

 

0.3

0.3

0.3

C20

4000:5

0.3

0.3

 

0.3

0.3

0.3

C10

5000:5

0.3

0.3

 

0.3

0.3

0.3

C10

bBreaker compartment will accept 3 CT’s in line on lower disconnects.

cBreaker compartment will accept 6 CT’s, 3 on lower and 3 on upper disconnects.

dBreaker compartment will accept 3 CT’s in staggered arrangement, 2 on lower and 1 on upper disconnects.

4

480V Metal Switchgear- Enclosed

CSI Section 16470

Siemens Electrical Products and Systems

59

 

Specification Guide

 

Image 11
Contents Industry Standards LV switchgear is typically installedGeneral Utility and Co-generation Facilities480V Metal-Enclosed Switchgear Finish Assembly ConstructionConstruction Details GeneralCircuit Breaker Compartments Control WiringMain and Ground Bus InsulationOptions Guide Form SpecificationsPrimary Disconnects LV Power Circuit BreakersTypical Breaker Features Circuit Breaker RackingCurrent Limiting Fuses Ground ConnectionDrawout Interlocks Arc Interruption Static Trip III Trip Unit LV Power Circuit Breaker Trip Unit Static Trip III Settings Tripping Actuator Shunt Trip Coil Ratings Accessories/ModificationsRL Breaker Static Trip Iiicpx Protective Relay FunctionsRL Breaker Accessories / Modifications cont’d Technical 11 Control Power Transformers-115C RiseVT, CPT, CT Data LV Power Circuit Breakers Ratings 17 Type RL Circuit Breaker Control Data 15 Type RLF Fused Circuit Breaker Ratings At 50/60 Hertz16 Type RL Circuit Breaker Operating Data 60 Hertz Basis Time/Current Characteristics of Static Trip III Trip Unit 20 Fused Element Weight in lbs. kg Weights and DimensionsDimensions 19 Breaker Element Weight in lbs. kgTie Breaker Sections and Combinations Front Views Auxiliary / Breaker Section Dimensions22 Breaker Section and Connection Weights in lbs. kga Breaker DesignationsIndoor Side View Indoor Floor Plan, Side ViewIndoor Floor Plan Outdoor Floor Plan Outdoor Floor Plan, Side ViewBus SpecificationsAssembly Codes and StandardsInstrumentation and Metering TestingCircuit Breakers Solid State Trip Units