Siemens 480V manual Construction Details, General, Finish, Assembly Construction

Page 3

480V Metal-Enclosed Switchgear

Construction Details

General

General

The Siemens 480 volt switchgear assem- bly consists of one or more metal- enclosed, vertical sections. Normally the end sections are designed to allow for installation of future sections.

Each vertical section consists of up to four individually enclosed breaker or auxil- iary compartments which are sized to provide uniform height.

Included in each assembly are various components such as circuit breakers, instrumentation and control equipment, transformers, relays, three-phase bus work, and all internal wiring, connectors, and other supporting equipment.

In accordance with ANSI C37.20.1, the maximum temperature for parts that are handled is 50°C. The main bus maximum temperature rise is 65°C above 40°C ambient. The temperature rise of the air surrounding the cable connection points is limited to 45°C above 40°C ambient.

Finish

During construction, the structural steel parts, panels, and compartments are all prepared for painting by a five-stage wash system. Standard finish color is light gray ANSI 61. If a different finish color is required, it is applied over the standard finish with conventional spray equipment and is allowed to air cure. The completed finish has a nominal 2 mils dry film thickness.

Assembly Construction

Siemens metal-enclosed power switchgear is constructed of preformed, full-depth, 14-gauge steel sheets bolted together and reinforced with cross-mem- ber braces to form a rigid, self-supporting compact assembly. The top and rear plates, and side sheets are all 14-gauge steel. When two vertical sections are mounted together, two sheets of 14- gauge steel separate adjacent circuit breaker compartments.

Bolted steel / glass polyester compart- ments housing each power circuit break- er are mounted in the vertical section to form the switchgear assembly. This iso- lates the circuit breakers from the bus / cable section and from adjacent circuit breaker compartments.

The bus / cable section includes main horizontal bus, riser bus, connections from the main bus to each set of primary disconnects, and load side copper run- back bus.

Grounded metal barriers can be provided to isolate the main bus from cable con- nections. Barriers are also available to isolate the incoming line to the main cir- cuit breakers from the main load bus of the switchgear.

c

b

a

e

d

aInter-Unit Wiring Trough

bMeter and Auxiliary Compartment c Ventilation and Lifting Structure d Telescoping Breaker Drawout Rails

e Ventilation Openings (RL-2000, RL-3200, RL-4000 and RL-5000)

4

480V Metal Switchgear- Enclosed

CSI Section 16470

Siemens Electrical Products and Systems

51

 

Specification Guide

 

Image 3
Contents Industry Standards LV switchgear is typically installedGeneral Utility and Co-generation Facilities480V Metal-Enclosed Switchgear Finish Assembly ConstructionConstruction Details GeneralCircuit Breaker Compartments Control WiringMain and Ground Bus InsulationOptions Guide Form SpecificationsPrimary Disconnects LV Power Circuit BreakersTypical Breaker Features Circuit Breaker RackingCurrent Limiting Fuses Ground ConnectionDrawout Interlocks Arc InterruptionLV Power Circuit Breaker Trip Unit Static Trip III SettingsStatic Trip III Trip Unit Tripping Actuator Shunt Trip Coil Ratings Accessories/ModificationsRL Breaker Static Trip Iiicpx Protective Relay FunctionsRL Breaker Accessories / Modifications cont’d 11 Control Power Transformers-115C Rise VT, CPT, CT DataTechnical LV Power Circuit Breakers Ratings 15 Type RLF Fused Circuit Breaker Ratings At 50/60 Hertz 16 Type RL Circuit Breaker Operating Data 60 Hertz Basis17 Type RL Circuit Breaker Control Data Time/Current Characteristics of Static Trip III Trip Unit 20 Fused Element Weight in lbs. kg Weights and DimensionsDimensions 19 Breaker Element Weight in lbs. kgTie Breaker Sections and Combinations Front Views Auxiliary / Breaker Section Dimensions22 Breaker Section and Connection Weights in lbs. kga Breaker DesignationsIndoor Floor Plan, Side View Indoor Floor PlanIndoor Side View Outdoor Floor Plan Outdoor Floor Plan, Side ViewBus SpecificationsAssembly Codes and StandardsInstrumentation and Metering TestingCircuit Breakers Solid State Trip Units