480V Metal-Enclosed Switchgear
Guide Form Specifications
Specifications
4
480V
reaching over the main and vertical bus. Bus bracing shall be equal to the short circuit interrupting rating of the lowest rated
Circuit Breakers
Circuit breakers shall be Siemens Type RL and shall be either electrically or manually operated as indicated on the data sheets (or drawings). Minimum interrupting rat- ings will be as defined on the data sheets (or drawings) and shall meet or exceed the interrupting ratings as defined by ANSI standards. (Option) Fused circuit breakers are to be the integrally fused type through the 2000 ampere frame size. 3200 and 4000 ampere frame sizes are to be sup- plied with separate drawout fuse carriages which are mounted in the same vertical section as the circuit breaker element and are to be key interlocked with the circuit breaker element such that the fuse carriage cannot be withdrawn unless the circuit breaker is locked in the open position. All fused circuit breakers are to be equipped with blown fuse lockout devices to prevent single phasing. The application of fused circuit breakers shall not reduce the amount of rear cable termination space which would have been provided with non- fused circuit breakers.
Circuit breakers are to be 600 volt class with nominal ratings as dictated by the system voltage. Circuit breakers shall be
Solid State Trip Units
Solid state trip units shall be Siemens
JStatic Trip III (basic device)
J(Option) Static Trip IIIC (adds communications capability)
J(Option) Static Trip IIICP (adds communications and power metering)
J(Option) Static Trip IIICPX (adds communications, power metering, and relaying functions)
Trip units shall be interchangeable so that any trip unit can be used with any frame size circuit breaker. The basic trip unit shall be a self powered,
Instrumentation and Metering
A wide variety of user defined metering and instrumentation options are available. They include Siemens 4720, 4700 & 4300 power meters, Siemens Static Trip III trip units, and traditional analog devices. For more detailed specification information on Siemens devices refer to bulletins SGFL 3181B, 3161A, and 3151B for 4720, 4700, and 4300 power meters, respectively; and
Current transformers shall have standard accuracy class ratings as defined by ANSI C37.20.1 and shall be mounted directly on the stationary primary disconnects in the circuit breaker compartment. Voltage trans- formers shall have a minimum 150VA thermal rating and shall be located in a metal enclosed metering compartment and shall be protected on the primary side with current limiting fuses.
Outdoor
(Option) Outdoor, NEMA 3R,
Front and rear doors are to be gasketed and hinged. Front doors, located at each end, are to include panic release door hard- ware, three point latches, and provision for padlocking. Rear doors shall be bolted. All exterior hardware shall be stainless steel.
An indoor access aisle approximately 42 in. (1067 mm) deep and accessible from either door is to be provided at the front of the switchgear
The switchgear is to include space heaters to prevent condensation of moisture. The aisle shall be provided with incandescent lights, convenience receptacle, and an ON
/OFF switch at each end to control the lights.
Finish
During construction, the structural steel parts, panels, and compartments shall be prepared for painting by a
Accessories
The following accessories are to be provided:
Jcrank for racking circuit breakers
Jlifting yoke for circuit breakers
Jcontainer of
J(optional) portable test set, type PTS4
Joverhead hoist for indoor switchgear
J(optional) test cabinet
Testing
Production tests in accordance with ANSI C37.20.1, ANSI C37.50, ANSI C37.51 and NEMA SG 5 shall be performed on the completed assembly. Certified copies of these tests shall be furnished upon request.
68 | Siemens Electrical Products and Systems | CSI Section 16470 | |
Specification Guide | |||
|
|