Siemens 480V manual RL Breaker Accessories / Modifications cont’d

Page 10

480V Metal-Enclosed Switchgear

LV Power Circuit Breakers

General

4

480V Enclosed-MetalSwitchgear

RL Breaker Accessories / Modifications (cont’d)

Operation Counter

A mechanically-operated, 5-digit non- resetable counter can be mounted beneath the breaker auxiliary switch. The counter is incremented by the action of the auxiliary switch operating mechanism.

Undervoltage Trip Device

The undervoltage trip device protects against a drop in normal bus voltage and functions to directly trip the breaker. Pickup occurs at 85 percent or less of rated value and dropout between 30 and 60 percent of rated value. Pickup and dropout are individually adjustable. Instantaneous or time-delayed operation can be provided. The static timing unit is adjustable from 0.04 to 4 seconds for time delay. This allows the system to distinguish between undervoltage conditions and momentary voltage dips.

Table 4.7 Undervoltage Trip Ratings

Nominal Control

Pickup

Dropout

Voltage

 

Voltage

Voltage

 

120

100

60

60 Hz AC

240 or

 

480a

DC

48

40

24

125

105

62

 

aNot available. Use 120 VAC undervoltage device with appropriate 240/120V or voltage transformer in cubicle.

Electrically Operated Interlock

This can be added to interlock two break- ers, preventing both from being closed at the same time. These electromechanical devices add an additional solenoid that must be energized before the breaker can be closed. When the interlock is de- energized, the breaker is held trip-free and cannot be closed electrically or manually. The interlock has a mechanical link that goes to the main shaft of the breaker. The interlock is held in the picked-up position when the breaker is closed. Once closed the interlock can be de-energized without tripping the breaker. There are no adjustments for pickup or dropout voltages. The interlocks are continuously energized.

Table 4.8 Interlock Coil Ratings

 

 

Voltage Range

Nominal Control

Pickup

Dropout

Voltage

 

Voltage

Voltage

60 Hz AC

120

104

36

240

208

72

 

 

48

38

15

DC

125

100

38

 

250

200

75

Automatic Trip Alarm Contact (with or without Lockout) (Bell Alarm)

The bell alarm contact is operated when the trip actuator operates in response to the Static Trip III trip unit. It indicates when the circuit breaker has tripped as a result of the static trip unit. The contact can control a local or remote auxiliary alarm for indication of an automatic trip or, by wiring in series with a breaker clos- ing coil, for interlocking to prevent circuit breaker closure until the circuit is reset. The contact must be reset manually or electrically (optional). The manually reset switch is available with a single-pole double-throw contact, or two single-pole single-throw contacts. The electrically reset switch is available with a single- pole single-throw contact.

If desired, a mechanical lockout option may be provided. This substitutes a manual reset for the automatically reset tripping actuator. In this case the breaker is held trip free until the lockout is manually reset.

Table 4.9 Bell Alarm Contact Ratings

Nominal

 

Bell Alarm Contact Ratings

 

(Amperes)

 

 

Control

 

 

 

Voltage

 

Continuous

Make

Break

60 Hz

 

120

10.0

10.0

10.0

AC

 

240

10.0

10.0

10.0

 

 

48

0.5

10.0

0.5

DC

 

125

0.5

10.0

0.5

 

 

250

0.25

10.0

0.25

1

Current Sensors

3 Ground Shoe Contact

5 Secondary Disconnects

2

PT Module (Optional)

4 Primary Disconnects

 

RL Circuit Breaker – Rear View

58

Siemens Electrical Products and Systems

CSI Section 16470

Specification Guide

 

 

Image 10
Contents Utility and Co-generation Facilities LV switchgear is typically installedGeneral Industry Standards480V Metal-Enclosed Switchgear General Assembly ConstructionConstruction Details FinishInsulation Control WiringMain and Ground Bus Circuit Breaker CompartmentsGuide Form Specifications OptionsCircuit Breaker Racking LV Power Circuit BreakersTypical Breaker Features Primary Disconnects Arc Interruption Ground Connection Drawout Interlocks Current Limiting FusesStatic Trip III Settings LV Power Circuit Breaker Trip UnitStatic Trip III Trip Unit Static Trip Iiicpx Protective Relay Functions Accessories/ModificationsRL Breaker Tripping Actuator Shunt Trip Coil RatingsRL Breaker Accessories / Modifications cont’d VT, CPT, CT Data 11 Control Power Transformers-115C RiseTechnical LV Power Circuit Breakers Ratings 16 Type RL Circuit Breaker Operating Data 60 Hertz Basis 15 Type RLF Fused Circuit Breaker Ratings At 50/60 Hertz17 Type RL Circuit Breaker Control Data Time/Current Characteristics of Static Trip III Trip Unit 19 Breaker Element Weight in lbs. kg Weights and DimensionsDimensions 20 Fused Element Weight in lbs. kgBreaker Designations Auxiliary / Breaker Section Dimensions22 Breaker Section and Connection Weights in lbs. kga Tie Breaker Sections and Combinations Front ViewsIndoor Floor Plan Indoor Floor Plan, Side ViewIndoor Side View Outdoor Floor Plan, Side View Outdoor Floor PlanCodes and Standards SpecificationsAssembly BusSolid State Trip Units TestingCircuit Breakers Instrumentation and Metering