ADTRAN T200 H2TU-R dimensions Cabinet Assembly, Rear View

Page 3

 

Pimary

Secondary

 

 

Fan Board

Fan Board

 

 

to Cable A

to Cable A

 

 

 

 

 

 

Surge Arrestor

 

 

 

 

Board for top Shelf

Door

 

 

 

 

Ground

 

 

 

 

Braid

 

 

 

 

 

 

 

 

Door Gasket

Gas Tube

 

 

 

 

Extractor

 

 

 

 

Pliers

 

 

 

 

 

Rear Door

A, B, and Spare

Surge Arrestor Board

 

Switch

Rear Door

for bottom Shelf

Cable Penetrations

 

Retainer

 

 

 

 

Ground

Connecting lug on

 

 

Buss

( cabinet bottom )

Figure 2. Cabinet Assembly, Rear View

OPEN

23"

 

 

Front door

 

 

20 7/16"

 

 

C/C

 

 

View is looking down with top cut away.

 

 

Mounting bolt hole center lines are 1 5/8" in from each edge.

 

Ground stud is 1 5/8" from rear edge.

 

 

Measurements shown are center to center (C/C).

 

 

Door width includes locking flange.

 

 

Cable penetrations are 1 7/8" in diameter.

 

 

Cabinet is 27" high not including cable stubs.

13 3/4" 20"

17" Pad mount brackets are 18" high.

Dimensions are tape rule derived and measured from

C/C

overall

outside the cabinet.

 

 

5 3/4" 3 1/4" cable dimensions +/- 1/8"

2 1/2" C/L

Ground

Lug

A

B

spare

Rear door

23 5/8"

overall

OPEN

Figure 3. Top View Cutaway With Installation

Measurements

Fan Operation and Indication

Two thermostatically controlled line powered cooling fans limit heat buildup. The primary fan energizes at about 110° F. The secondary fan energizes at about 150° F.

Primary and secondary fan board operation is monitored by the FPU. The following conditions cause an alarm at the FPU:

Any fan or fan board not receiving power.

Secondary fan turning On.

Open cabinet door.

The single FPU at the CO has a separate power supply for each fan board. The FPU fits into one slot of the E220 HTU-C shelf (for HDSL applications).

The FPU is purchased separately. Information on fan board operation and testing is in Section 3. For additional details on the FPU refer to I&M Practice: 61150091L1-5. The FPU Practice should be on-hand at the CO for reference during cabinet testing.

61150090L1-5A

Section 61150090L1-5A, Issue 1

3

Image 3
Contents Description GeneralRevision History Practice ReviewMounting FeaturesCabinet Access T200/T400 Cabinet Basic FeaturesCabinet Assembly, Rear View Pad Mount Installation Status Indicator LEDsDoor Power LED InstallationLifting Detail Assembly Pole Mount Installation Pad Mounting Bracket InstallationPole Mount Hardware Mounting Bracket AssemblyFrame Mount Bottom Support Bracket AssemblySeal Grommet Kit Cable Stub EntryII. Shielding Shield Connector AssemblyIII. SHRINK-WRAP Splice Module Splice ModuleFnid Circuit Technology Configuration Chart PartCable Pair Tip Ring Fan Board Indication Testing GeneralDoor Switch Verify Power at the Fan BoardsAbnormal Condition Turning the Secondary Fan On Fan Board TroubleshootingFan Operation Verify Proper ConnectionsOpen Loop/No Continuity Door Switch TroubleshootingDoor Switch Failure-Closed Door Switch Failure-OpenDesiccant Renewal MaintenanceReplacement Item Part Numbers Surge Arrester ReplacementDoor Gasket Replacement Warranty and Customer Service Customer & Circuit Information