ICP DAS USA 7000 user manual This is the third function

Page 74

rates are different. For example, ￿7xxx=module address 01, baud rate=1200 ￿7xxx=module address 01, baud rate=9600 ￿7xxx=module address 01, baud rate=115200

These three modules can share the same RS-485 network, generated by ￿7520.

(4)Therefore there is 256*8=2048 modules max. In one RS-485 network with a repeater (7510).

The “search function” given in NAP7000S can search for all these 2048

modules in one RS-485 network. Refer to “NAP7000S User Manual” for completely source listing of “search function”.

When the RS-485 network is over 4000 ft or 1.2Km, the RS-485 repeater (7510) must be added to extend the RS-485 network. For example, if the ￿RS-485 is over 4000 ft or 1.8 Km, the ￿7510 must be added to extend ￿RS-485 to ￿RS-485. And if the ￿RS-485 is too long, the user should use another 7510 to extend another RS-485 network. This is the second function of 7510.

The power ground of the 7000 series is common ground to the RS-

485 network. This feature is the same as the Adam 4000, Nudam 6000

and DATAFORTH 9B series. Therefore all the modules in the same RS-

485 network are common ground. For example, the all modules between ￿7xxx and ￿7xxx share the same ￿RS-485 network and all are common ground. The ￿RS-485 length can be up to 4000 ft or 1.2 km, this is a very long path. This long path makes the RS-485 network very susceptible to

network noise by high energy transient in this environment. If this noise is

too great, all the modules in the RS-485 network may be damaged

simultaneously. This is highly possible and occurs often in real world applications. It is strongly recommended to add another isolation repeater, the 7510, to break the long path RS-485 network into several short RS- 485 networks to avoid all the modules being damaged at the same time.

This is the third function of 7510.

7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10) ---------------

74

Image 74
Contents 7000 Series Bus Converter 7520 Pin Assignment and Specifications Block Diagram Common Features of the 7000 SeriesDimension 7000 series overview7510 7513PC Networking Applications RS-232 Devices Network Quick Starting the 7000 SeriesIntroduction Group 10 Power supply module ACE-540A 24V/2A power supply Page Page Page Page Back View Stack Mounting Din Rail Mounting 7520/A/R/AR, PCI-7520AR, PCISA-7520R Isolation voltage3 I-7520 is designed Termination resistor 120 Ohm on board Remove resistorI-7520R Pin Assignment and Specifications 7520R RS-232 to RS-485 ConverterI-7520A Pin Assignment and Specifications 7520A RS-232 to RS-422/485 ConverterDefault sitting Ohm on board JP1JP3 I-7520AR Pin Assignment and Specifications 7520AR RS-232 to RS-422/485 ConverterNot Connect PCI-7520AR Pin Assignment and SpecificationTerminal Wire RS-485 Wire RS-422 PCISA-7520R Pin Assignment and Specification Terminal Wire RS-4857000 Host Computer 7520 Page Therefore the Host PC/PLC is common ground with NetworkHost PC/PLC Power Ground with Host PC/PLC forUses the same DC If there is high voltageConfiguration B 7560 / I-7561 I-7560 Pin Assignment and Specifications IntroductionI-7560 System Network Configuration Block Diagram 3 I-7560 Driver Installation Installing the DevicePage Page Page Page Page Page Page I-7561 Pin Assignment and Specifications SpecificationsPage Set Type Channels RS-485 4 I-7561 is designed Termination resistor 120 Ohm on boardJP3 Page Page Page Page Page Page Page Page Page Page Page Page I-7563 Pin Assignment and Specifications 7563Page Page Page Page Page Page Page Page Page I-7551 Pin Assignment and Specifications RS-232 TxD, RxD, CTS, RTS, GND or TxD, RxD, DCD, DTR, GNDPage 7510 / I-7510A / I-7510AR I-7510A Pin Assignment and Specifications 7510A RS-485/RS-422 RepeaterI-7510AR Pin Assignment and Specifications 7510ARPage 7513 Page Page RS-485 Networking This is the third function GND Page PLC Networking Applications RS2PC Networking Applications RS-485 Series 7520 Host PC RS-232 device Find Status of Unknown Module Wire connection Refer to Sec Quick Starting the 7000 SeriesChanging Module Address Wire connection Refer to Sec Press $02FEnterChanging Baud Rate Wire connection Refer to Sec Checksum Enable/Disable Wire connection Refer to Sec Press $012Enter Receive=!01080640B1Checksum=0