7.Quick Starting the 7000 Series
7.1Find Status of Unknown Module
Wire connection: Refer to Sec. 2.7
Test program: Refer to “NAP7000S User Manual” for TEST.EXE
Connect I NIT*_pin to GND_pin first as follows.
The steps to finding the status of an unknown module are given as follows.
1.Wire connection, INIT*_pin=GND, power on and run test.exe
2.Press 2
3. | Press $002[Enter] | Receive=! 02080A40 |
4. | Press 2 |
|
5. | Press %0001080600[Enter] Receive=! 01 |
6.Power off, disconnect INIT*_pin (pin 6) and GND_pin (pin_10) and power on
7.Press 2
8. | Press $012[Enter] | Receive=! 01080600 |
9. | Press 2 |
|
10. Press $01M[Enter] | Receive=! 017017 | |
11. | Press 2 |
|
12. Press $01F[Enter] | Receive=! 01A1.3 | |
| Step 3: read the | module status with the INIT*_pin connected to the |
GND_pin and find that module address=02, baud rate= 115200, checksum is enable.
Step 5: change this module to address=01, baud rate=9600, checksum
disable
Step
NOTE: If the
(1)Module address=00; (2) baud rate=9600; (3) checksum is disable
7000 Bus Converter User Manual (version 1.2,Feb/2003, | 80 |