![](/images/new-backgrounds/1230191/230191161x1.webp)
7.2Changing Module Address
Wire connection: Refer to Sec. 2.7
Test program: Refer to “NAP7000S User Manual” for TEST.EXE
The steps to change module address are given as follows.
1.Wire connection, power on and run test.exe
2.Press 2
3. | Press $012[Enter] | Receive=! 01080600 |
4. | Press 2 |
|
5. | Press %0102080600[Enter] Receive=! 02 | |
6. | Press 2 |
|
7. | Press $022[Enter] | Receive=! 02080600 |
8. | Press 2 |
|
9. | Press $02M[Enter] | Receive=! 027017 |
10. Press 2 |
| |
11. Press $02F[Enter] | Receive=! 02A1.3 |
•Step 3: read the module status and find that module address=01, baud rate= 9600, checksum is enable.
•Step 5: change the module address from 01 to 02, the module address can be changed immediately, no need to
•Step 7: read the module status based on the module address=02
•Step 9: read the module name
•Step 11: read the firmware number of this module
NOTE: If the user uses $AA2 command to change module configuration, the new configuration code will be stored into EEPROM immediately. The configuration code includes module address, module type, baud rate code, checksum enable/disable code, calibration code,
7000 Bus Converter User Manual (version 1.2,Feb/2003, | 81 |