It is recommended to use the “trial and error” rule. The trial and error rules are given as follows:

(1)If the length of RS-485 is about 1.2 Km, try 120first

(2)Run TEST.EXE of NAP7000S

Select function_5, run continuously for at least 8 hours to make sure communication is OK.

(3)If function_5 finds many communication errors, use an oscilloscope to check the waveform. The waveform will tell you

whether the terminator is too small or too big. Then adjust your terminator and run TEST.EXE again.

(4)

(5)If the correct terminators are found, run the TEST.EXE continuously for at least 8 hours to make sure there are no communication errors.

The function_5 of TEST.EXE, given in NAP7000S, will automatically read “testing command” from TEST.DAT and continuously perform “send- receive-testing”. It will continuously test and record all testing results. Therefore this function is especially designed for RS-485 network stability

evaluation. If you run this function_5 continuously for 8 hours and find no

check errors, this means that your RS-485 network is very stable. Also

this means that your terminators match well now.

NOTE 1: The value of the terminator depends on the RS-485 wire used. If the RS-485 path is very long, don’t use a cheaper wire. It is recommended to select a high quality wire such as the Belden 1583A.

NOTE 2: The terminator is different for various applications. Therefore we can’t provide a terminator with the 7520 or the 7510. The user must choose the correct terminator by them self. It is recommended

to use a carbon, 1/4w resistor.

7000 Bus Converter User Manual (version 1.2,Feb/2003, 7PH-006-10) ---------------

76

Image 76
Contents 7000 Series Bus Converter Common Features of the 7000 Series Dimension7520 Pin Assignment and Specifications Block Diagram 7000 series overview7510 7513PC Networking Applications RS-232 Devices Network Quick Starting the 7000 SeriesIntroduction Group 10 Power supply module ACE-540A 24V/2A power supply Page Page Page Page Back View Stack Mounting Din Rail Mounting 7520/A/R/AR, PCI-7520AR, PCISA-7520R Isolation voltage3 I-7520 is designed Termination resistor 120 Ohm on board Remove resistorI-7520R Pin Assignment and Specifications 7520R RS-232 to RS-485 ConverterI-7520A Pin Assignment and Specifications 7520A RS-232 to RS-422/485 ConverterDefault sitting Ohm on board JP1JP3 I-7520AR Pin Assignment and Specifications 7520AR RS-232 to RS-422/485 ConverterTerminal Wire RS-485 Wire RS-422 PCI-7520AR Pin Assignment and SpecificationNot Connect PCISA-7520R Pin Assignment and Specification Terminal Wire RS-4857000 Host Computer 7520 Page Therefore the Host PC/PLC is common ground with NetworkPower Ground with Host PC/PLC for Uses the same DCHost PC/PLC If there is high voltageConfiguration B 7560 / I-7561 I-7560 Pin Assignment and Specifications IntroductionI-7560 System Network Configuration Block Diagram 3 I-7560 Driver Installation Installing the DevicePage Page Page Page Page Page Page I-7561 Pin Assignment and Specifications SpecificationsPage Set Type Channels RS-485 4 I-7561 is designed Termination resistor 120 Ohm on boardJP3 Page Page Page Page Page Page Page Page Page Page Page Page I-7563 Pin Assignment and Specifications 7563Page Page Page Page Page Page Page Page Page I-7551 Pin Assignment and Specifications RS-232 TxD, RxD, CTS, RTS, GND or TxD, RxD, DCD, DTR, GNDPage 7510 / I-7510A / I-7510AR I-7510A Pin Assignment and Specifications 7510A RS-485/RS-422 RepeaterI-7510AR Pin Assignment and Specifications 7510ARPage 7513 Page Page RS-485 Networking This is the third function GND Page PLC Networking Applications RS2PC Networking Applications RS-485 Series 7520 Host PC RS-232 device Find Status of Unknown Module Wire connection Refer to Sec Quick Starting the 7000 SeriesChanging Module Address Wire connection Refer to Sec Press $02FEnterChanging Baud Rate Wire connection Refer to Sec Checksum Enable/Disable Wire connection Refer to Sec Press $012Enter Receive=!01080640B1Checksum=0