It is recommended to use the “trial and error” rule. The trial and error rules are given as follows:
(1)If the length of
(2)Run TEST.EXE of NAP7000S
Select function_5, run continuously for at least 8 hours to make sure communication is OK.
(3)If function_5 finds many communication errors, use an oscilloscope to check the waveform. The waveform will tell you
whether the terminator is too small or too big. Then adjust your terminator and run TEST.EXE again.
(4)
(5)If the correct terminators are found, run the TEST.EXE continuously for at least 8 hours to make sure there are no communication errors.
The function_5 of TEST.EXE, given in NAP7000S, will automatically read “testing command” from TEST.DAT and continuously perform “send-
evaluation. If you run this function_5 continuously for 8 hours and find no
check errors, this means that your
this means that your terminators match well now.
NOTE 1: The value of the terminator depends on the
NOTE 2: The terminator is different for various applications. Therefore we can’t provide a terminator with the 7520 or the 7510. The user must choose the correct terminator by them self. It is recommended
to use a carbon, 1/4w resistor.