Sterling 1-Pump 5-Station Controller Connecting the Control Panel to the Pump Package

Page 21

VDC) as the SSC control panel voltage. Consult the control panel serial tag and the solenoid valve nameplates.

4.Wire size depends on control voltage, distance, number of vacuum receivers, and the number of wires in each raceway. Consult a qualified electrician.

5.Properly ground each receiver to reduce static build up generated by material conveying.

4-5 Connecting the Control Panel to the Pump Package

1.Wire the pump package motor starter coil (M) to the terminal provided in the SSC control panel enclosure.

2.Wire the pump package vacuum relief valve solenoid (SOL A) to the terminal provided in the SSC control panel enclosure.

3.Wire the pump package vacuum switch (VS) to the terminal located in the SSC control panel enclosure (If provided).

4.On SPDB pumps, wire the pump package blowback solenoid (SOL B) to the terminal located in the SSC control panel enclosure.

Wire the pump package motor overload to the terminal provided in the SSC control panel enclosure.

5.On 24 VDC control voltage systems, run a common +24 VDC wire and a common 0 (zero) VDC wire from the controller to each pump package in the conveying system.

4-6 Special Timed Convey

Connect +24 VDC to inputs 11-15, corresponding to Stations 1-5, to enable the Special Timed Convey feature.

Page 20 of 38

Image 21
Contents SSC1-5Q Model # Serial # Parts and Service Department Table of Contents Configurable Settings Charts and Figures Safety Considerations Sterling SSC1-5Q Conveying Systems Pump 5-Station Controller Equipment Function General InformationNecessary Documents System CapabilitiesEquipment Cycle Models Covered by this ManualSSC1-5Q 5-Station Controller SSC1-5Q Controller Safety Considerations SafetyWork Rules Tools and Equipment NeededGeneral Responsibility Reporting a Safety DefectOperator Responsibility Maintenance ResponsibilitySafety Devices Safety Circuit StandardsFail Safe Operation Safety Device Lock-Outs Page Unpacking and Inspection Shipping InformationEvent of Shipping Damages Parcel Post ShipmentIf the Shipment is Not Complete United Parcel Service ShipmentIf the Shipment is Not Correct ReturnsInstalling the SCC1-5Q Control Panel InstallationMaking SSC1-5Q Control Panel Power Drop Wiring Connections Connecting the Control Panel to Vacuum ReceiversSpecial Timed Convey Connecting the Control Panel to the Pump PackageSetup Using the ControllerSetting Up the System Basic Menus and Setup of ControllerSetting Blowback Parameters Setting Pump ParametersStarting the System Changing ParametersLong Tones High vaccum alarm will sound in Short TonesOptions for Station Setup 6Configurable SettingsIdle Options for Pump Setup7Maintenance General Troubleshooting TroubleshootingAlarms Station AlarmsPump Alarms Options Remote Audible/visual alarm230/1/60 Operation CE Package for 220/1/50 OperationRecommended Spare Parts List Spare Parts ListContact Information for Technical Assistance Technical AssistanceWarranty Returns Returned Material PolicyCredit Returns Warranty Safety Tag Information Controller Safety TagsController Identification Serial Number Tag Appendix Page Service Department