Studer Innotec RCC-03, RCC-02 user manual Configurations for auxiliary contacts 1 and 2 1201

Page 38

Studer Innotec

Delay before passing to inverter {1198}

When the input voltage is below the transfer voltage to the inverter, the transfer relay does not open immediately. With this configuration, the period during which the transfer remains drawn can be specified. After this duration, the transfer relay is opened and the inverter function is activated (if the function has not been blocked or deactivated).

This delay is particularly useful on less stable grids or with generators with an output voltage that varies considerably during the activation of heavy loads.

Immediate transfer AC-In voltage {1200}

Use the adjustment of this configuration to adjust the critical voltage for the operation of equipment that must not experience interruptions. In the case of a fluctuating grid, if its voltage passes below the value of the configuration this immediately activates the inverter function, thereby ensuring supply to the consumers.

Activate immediate detection of grid outage (UPS) {1435}

This parameter allows to starting the inverter mode as quick as possible in case of fluctuations of the AC-In grid. This function is useful when it comes to very sensitive loads that require an uninterruptible power supply (UPS). If this function is active, being connected to a fluctuating source (weak grid or unstable generator) will lead to a frequent switching between inverter and charger modes by opening and closing of the transfer relay.

Authorisation for exceeding the power sharing current without interrupting the transfer {1436}

The parameter {1107} allows you to adapt the running of the Xtender to the maximum power of the source. In case this value is overrun, the transfer relay is not open and the circuit breaker on the source side may go on default. With this parameter you can force the transfer relay to open itself and the Xtender to work in inverter mode.

Use this function if you have available a source that is smaller than the Xtender and if you don’t use the function Smart-Boost. In this way, in case of overload of the source, all the power is supplied by the Xtender, up to its own limits.

Solsafe presence {1438}

This parameter allows the connection on the AC-Out side of an inverter for grid feeding. It also authorizes the Xtender to accept the energy coming from the output and to use it to charge the batteries.

Delay before closing of the transfer relay {1528}

This parameter enables to delay the closing of the transfer relay even if the AC-In voltage is present.

This function can be useful while working with gensets having a pre-warming delay.

Configurations for auxiliary contacts 1 and 2 {1201} {1310}

The Xtender inverter/charger is equipped with two auxiliary relays each with one free of potential contact (reverser). These two relays allow multiple functions to be carried out by using adequate cabling as well as simple programming.

The programming of each contact is carried out independently except when conditions require the use of two relays. In this case, the programmed events for activating the second relay are automatically deactivated.

The extended functions of the auxiliary contacts are described at the end of the chapter on simple functions.

The auxiliary contacts are activated immediately in response to the programmed signals. When the activation conditions are no longer fulfilled, they are deactivated with a delay of 2 seconds to avoid overswitching.

38

Image 38
Contents Studer Innotec Rue des Casernes CH 1950 Sion Studer Innotec Table of contents Maximum current of the AC source power sharing RCC Studer Innotec Product Recycling ForewordConventions Studer Innotec Contact Details Your RESELLER’ Contact DetailsAcceptance of the Software Licence and Updates WarrantySafety Instructions Limitation of ResponsabilityStuder Innotec Models Concerned Controls and IndicatorsIntroduction SD CardConnection Series ConnectionDimensions RCC-02 RCC-03Adaptation to the Source Adjustment of the LanguageQuick Start Guide Adaptation to the Batterie Activation of the Function SMART-BOOST Basic Displays Activating and Deactivating the Combi Xtender Adjustment of the Contrast Adjustment of the RCC Remote ControlAdjustment of Date 5002 and Time Adjustment of the BACK-LIGHTINGBackup of statistics Duration of the back-lightingLoading the remote control configurations Backup of remote control configurationsBackup of Xtender configurations Loading the Xtender configurationsInformation on the Operating Mode of the Installation Display of the Parallel and THREE-PHASE Systems Stop High Battery Voltage Alarm LOW Battery VoltageStop Battery Voltage TOO LOW Event HistoryError Input Voltage TOO LOW Error Incorrect Input FrequencyError Input Voltage TOO High Stop OvertemperatureError Phase not Defined Message Power Sharing Exceeded Transfer ProhibitedError Voltage AT AC OUT Stored EventsAdjustment of the Combi Xtender Locking Basic configurationsMaximum current of the AC source power sharing Authorised inverterSmart boost authorised Automatic restartAuthorised charger Authorised transferBattery cycle and charger Restore default configurationsRCC Studer Innotec Force passage to floating mode Temperature correction coefficientBattery maintenance voltage floating Charge currentAbsorption phase Equalization phaseEqualization voltage Equalization before absorption phaseEqualization current Duration of equalizationOutput voltage Inverter configurationsStandby level End of equalization activated by the currentCombi configurations Inverter-Charger Configurations for auxiliary contacts 1 and 2 1201 Simple functions Switching mode 1202Combination of events mode 1497 Temporal restrictions 1203 Battery undervoltage alarm 1226Battery overvoltage 1227 Contacts activated by an event 1455Contacts activated by the battery voltage 1245 Contacts activated with set schedules 1269 Contacts activated by inverter power or smart boost 1257Deactivate if the battery is in floating mode 1516 Dynamic compensation of the thresholds 1288Multi Xtender Phase integral modeExtended functions Xtender Remote ControlsInformation on the System Compatibility UpdatesUpdating Process Général USE INVERTER, Charger with Grid USE of a Limited Power SourceApplication Examples USE to Increase the Power on AN Existing Installation Load Shedding of the Second Priority LoadsAnnexe 1 List of Configuration Interdependencies AnnexesRCC Studer Innotec RCC

RCC-03, RCC-02 specifications

Studer Innotec, a renowned Swiss company in the field of power electronics, has made significant strides with its range of battery management systems, particularly the RCC-02 and RCC-03 models. These units are renowned for their cutting-edge technologies, impressive features, and superior performance in managing energy systems for both off-grid and hybrid applications.

The RCC-02 and RCC-03 Remote Control Displays provide end-users with an intuitive interface to monitor and control their energy systems seamlessly. With a clear and easy-to-read display, these units offer real-time data, allowing users to view essential information such as battery voltage, current, and state of charge. This vital information empowers users to make informed decisions regarding energy consumption and system management.

One of the standout features of the RCC-02 and RCC-03 models is their compatibility with a wide range of Studer Innotec products, including inverters and battery chargers. This versatility ensures seamless integration into existing systems, making it an ideal choice for both new installations and upgrades of existing systems.

Both models incorporate advanced communication technologies such as RS-232 and CAN-bus, allowing for easy data logging and system monitoring. This connectivity not only ensures that the user has access to real-time data but also enables remote monitoring and diagnostics, significantly enhancing the overall user experience.

Another characteristic that sets the RCC-02 and RCC-03 apart is their robust design. These units are engineered to withstand the harsh conditions often found in off-grid environments, ensuring reliability and durability over an extended lifespan. The thoughtful design also includes user-friendly controls, making it easy to configure settings and manage system parameters for a wide array of applications.

Energy efficiency is paramount in today's energy-conscious world, and the RCC-02 and RCC-03 are designed to optimize battery usage. By providing timely information about battery status and energy flow, these units assist users in maximizing the lifespan of their batteries and ensuring that their energy resources are used effectively.

In summary, Studer Innotec’s RCC-02 and RCC-03 Remote Control Displays are essential components for anyone looking to harness the power of reliable battery management systems. With their advanced technologies, user-friendly interfaces, and robust construction, they represent the cutting edge of energy management in both off-grid and hybrid applications. Whether for residential, commercial, or industrial use, these units deliver efficiency, reliability, and peace of mind to users.