PC | CH1 |
|
|
|
|
|
|
|
| ||
| CH2 |
|
|
|
|
|
|
|
| CM | LOOP TEST |
|
|
|
| ||
|
|
|
| CABLE | |
|
|
|
|
| |
|
|
|
| ||
|
| NCM |
|
| |
|
| MODULE |
|
| |
|
| MODULE |
|
| |
|
| ADAPTER |
| ||
|
|
|
| ||
|
|
|
|
| |
|
|
|
| CM |
|
|
|
|
|
| |
|
|
|
|
| |
|
| IMUX 2000 DROP/INSERT MULTIPLEXER | RS232 |
| |
|
|
|
|
Figure 11. Simplified block diagram, loop test for RFL NCM module in NMS mode, installed in a DI-B configured multiplexer.
9.Go to “Setup” on the toolbar in NMS, and select “Communication Preferences”. Check the “Change Advanced Settings” box, and enter the NCM/CM address into the “Assume Communication Works/Comm to node #”. Click “OK”.
10.Check “Read” Icon and check the “Auto Configure” box. Then select Method 3 and then click “OK”. Then click “OK” again and proceed with the read. Commands sent to and responses from the CM (via the NCM) should be evident in the communications window. IN1 (DS1), OUT2 (DS2), IN2 (DS3), and OUT2 (DS4) will illuminate green when data is present at the respective port.
11.Once the Read of the node has concluded, click the NetVw Icon. The node corresponding to the NCM/CM address should be present. Select this node by clicking on it. Verify that the “NCM” module is present in the list.
12.Select “NCM” and click the view button. Verify that all NCM settings are correctly set. (i.e. address passing mode)
13.Disconnect the patch cord from the
If the above test procedure can be successfully completed, the RFL NCM module is functioning properly. If not, use standard troubleshooting procedures to isolate the problem to the module itself, to another module in the IMUX 2000, or to the T1 or E1channel. If the problem lies in the RFL NCM module, replace it with a spare.
RFL NCM |
| RFL Electronics Inc. |
November 6, 2007 | 32 | (973) |