RF-Link Technology Network Communications Module, RFL NCM CM Address Pass Settings, NMS Mode only

Page 45

Table 6. continued - Remote configuration settings (“P” codes)

P Code

Digit(s) And Switch Equivalent

Value (1)

Description

P06

B 0 0 0 0 0 0 0 0

00

Any CM Address

 

↑ ↑ - - - - - -

01

Equal To

 

CM ADDRESS PASS SETTINGS

10

Equal To Or Greater Than (Force FDL Search)

 

(NMS MODE ONLY)

11

Equal To Or Less Than (Force FDL Search)

 

 

 

 

 

B 0 0 0 0 0 0 0 0

000

Broadcast

 

- - - ↑ ↑ ↑ - -

001

NMS

 

APPLICATION MODE

010

Master

 

SETTINGS

 

 

 

 

011

D&I Slave (Bus Direction Points Towards Master)

 

 

100

End Slave (Bus Direction Points Towards Master)

 

 

101

Mode is undefined

 

 

110

Mode is undefined

 

 

111

Mode is undefined

 

B 0 0 0 0 0 0 0 0

0

Port 2 Disabled

 

- - - - - - -

 

 

 

PORT 2 ENABLE SETTINGS

1

Port Enabled

 

 

 

 

 

B 0 0 0 0 0 0 0 0

0

T1/E1 and Port Rogue Detection Disabled

 

- - - - - - -

 

 

 

ROGUE SETTINGS

1

T1/E1 and Port Rogue Detection Enabled

 

 

 

 

 

B 0 0 0 0 0 0 0 0

Not used

 

- - - - - - -

 

 

 

 

 

 

P07

B 0 0 0 0 0 0 0 0

Not used

 

↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑

 

 

 

 

 

 

P08

B 0 0 0 0 0 0 0 0

Not used

 

↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑

 

 

 

 

 

 

P09

B 0 0 0 0 0 0 0 0

Not used

 

↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑

 

 

 

 

 

 

P10

B 0 0 0 0 0 0 0 0

Not used

 

↑ ↑ ↑ ↑ ↑ ↑ ↑ ↑

 

 

 

 

 

 

RFL NCM

 

RFL Electronics Inc.

November 6, 2007

45

(973) 334-3100

Image 45
Contents RFL NCM DescriptionRFL NCM NMS Mode Ascii Character Addressing Format SpecificationsInstallation RFL NCM MA-402I Module adapter, connector pinouts MA-485 Module adapter, jumper functions and TB1 pinouts MA-490 RFL NCM Front Panel View of RFL NCM, Network Communications Module Typical network example with all nodes having an NCM module At node 3, SW7 is set as follows Controls and indicators, RFL NCM Module Name/Description Function RFL NCM PRA Actel probe a NMS NMSDown SW2-3 SW2-4 Do not move SW10-4 Functional Description Block diagram, RFL NCM moduleSystem Overview TX Input Ports NCM Backplane and Power ConnectionsRX Output Ports Logic Array Actel DesignApplication Modes and Interfaces SCB ModuleUart Receive Section T1 Transmit Module Uart Transmit SectionRogue Control T1 Receive ModuleLOOP-BACKS Baud and Clock GeneratorPower indicator should be lit TestingService LED should be illuminated green Test Equipment RequiredDS1 Power indicator should be lit DS1-B Equip OUT RXA LED should be illuminated red CH1 DS1-B Equip OUT CH2 NCM General Configurations and Status window for Node Remote Control Using NMSE1 Signaling Module EnableTime Slot ModeTypical 3-node network using MA-485s 1 RS-485 port Rogue Detection Bus a & Bus BLocal CM Address NCM Address Configurations and Status window for NodeCM Address Passing Baud Rate Data BitsParity Troubleshooting Port 2 EnableLoopback Remote Control Using SCL Commands Channel Card 3, Type 117 Under Remote Control Svce = onCodes Srvc = on Srvc = OFF Multiplexer Addresscard ADDRESSSETP1 = B00000011BUS B Setting BUS a SettingCAS Setting Timeslot SelectionBaud Settings Port Loopback SettingsParity Settings Word Length SettingsNMS Mode only CM Address Pass SettingsApplication Mode SettingsCodes Type ID MUX Type & Configuration StatusPort 1 Availability Port 2 AvailabilityCM Addressing Support Application Configuration StatusPort 1 Application Status Port 2 Application StatusCurrent Actel REV RXA Remote CM AddressPort 2 INPUT/OUTPUT Status Port 1 INPUT/OUTPUT StatusTXB/RXA Status for T1/E1 TXA/RXB Status for T1/E1Powerville Road