American Dryer Corp T30 Regulated Gas Valve, Conversion from Propane or Butane Gas to Natural Gas

Page 25

Regulated Gas Valve

Refer to “Gas Pressure Adjustment” on this page to adjust the gas valve to the appropriate burner pressure listed on page 22. The supply pressure must also match what is listed on page 22 for the type of gas to be used.

Important

!Conversions done improperly can result in a fire or explosion!

Conversion from Propane or Butane Gas to Natural Gas

The following conversion allows the dryer to be operated with natural gas.

Parts Required for Conversion:

Description

P/N

Qty

Vent Cap and Spring

140415

**

Burner Orifice (Injector)

*

**

*Refer to page 22 for orifice (injector) size.

**T20 and T30 will require 1; T50 and T75 will require 2.

Instructions

Disconnect electrical power to the dryer.

Close all shutoff valves in dryer’s gas supply line.

Important

!The T50 and T75 will require that the following procedures be performed on both burner

assemblies.

Open the panel located just below the loading door.

Locate the gas train and disconnect the union, 3 electrical plugs, and the gas train mounting screws from the burner. Carefully slide the gas train out of the gas train enclosure. (The carbon ignitor located at the far end of the gas train is very fragile.)

Remove 2 burner tube mounting screws and remove burner tube in order to gain access to the orifice.

Using a 3/8” wrench or socket, remove the existing orifice and replace it with an orifice from the kit.

Important

!Use extreme care when removing and replacing orifice (injector). This orifice (injector) is made of

brass, which is easily damaged.

Reinstall the burner tube onto the burner base.

Select from the following 3 options, the conversion to be performed:

Converting from unregulated L.P. to regulated natural gas: use a flat screwdriver to remove the cap with blocking pin and install the regulator vent cap from the kit (P/N 140415).

Converting from unregulated L.P. to unregulated natural gas: no change to the regulator is required.

Converting from regulated L.P. to regulated natural gas: remove the white plastic regulator adjustment screw (under vent cap). Remove spring under screw and replace with spring from kit (P/N 140415). Replace regulator adjustment screw.

Install the gas train back into the dryer gas train enclosure. Be sure the tab at the rear of the gas train engages into the mounting slot.

Connect the union and the 3 electrical plugs.

Open all shutoff valves, reconnect electrical power to the dryer, and test for leaks.

Operate the dryer through 1 complete cycle to ensure proper operation.

With dryer operating, check the manifold (burner) pressure at the tap on the gas valve to ensure proper operating pressure (refer to chart on page 22).

Gas Pressure Adjustment

Disconnect electrical power to the dryer.

Important

!The T50 and T75 will require that the following procedures be performed on both burner

assemblies.

To adjust gas valve’s internal regulator, remove the regulator vent cap with the regulator adjustment tool, which is located on the back guard between the gas inlet and exhaust outlet (refer to the illustration below for proper use of adjustment tool). Be sure to use one of the wide ends of the adjustment tool for removal of the vent cap. Once vent cap is removed, the narrow end of the adjustment tool can be used to turn the plastic adjustment screw in the valve. Turn the screw clockwise to raise pressure and counterclockwise to lower pressure.

Gas (burner) pressures are measured with the burner in operation for all burner adjustment conditions. Therefore once the necessary adjustments have been made, the dryer must be operated in a heating cycle to verify that the pressure is correct. If it is not correct, you must discontinue the power to the unit and make further adjustments. Repeat these steps as many times as necessary to achieve the correct burner pressure. Once the adjustment of the valve is complete, the vent cap must be replaced and sealed with, for example, paint to prevent maladjustment by the user.

Edge #1 for vent cap

Edge #2 for adjustment screw

Warning (CE Dryers)

!This appliance must only be operated with the gas type indicated on the dryer’s data plate. If the

appliance is converted (gas type changed), a data plate amendment must be obtained from JLA Limited.

Conversions done improperly can result in a fire or explosion!

113429 - 9

Telephone 01422 822282

25

Image 25
Contents JLA Limited T20 / T30 / T50 / T75 Installation/Operator ManualRetain This Manual in a Safe Place for Future Reference Table of Contents What To Do If You Smell Gas Safety PrecautionsCE only 33.02 cm T20 SpecificationsT20 Specifications 37.78 cm T30 SpecificationsT30 Specifications 40.64 cm T50 SpecificationsT50 Specifications T75 Specifications T75 Specifications Unpacking/Setting Up Installation ProceduresLocation Requirements Dryer Enclosure RequirementsExhaust Requirements Fresh Air Supply RequirementsDomestic Type I T20, T30, T50 Only Single Dryer Venting Outside Ductwork ProtectionHorizontal Venting Vertical VentingElectrical Requirements Electrical InformationT20 Electrical Service Specifications Gas Models OnlyT30 T50Electric Models Only Single-Phase 1ø Wiring Connections/HookupGrounding Electrical ConnectionsElectrically Heated Models Only Two Element Configuration Three Element ConfigurationCE Dryers Gas InformationDMS Piping/Connections T20 T50Converting from One Family Gas to Another Regulated Gas Valve Gas Pressure AdjustmentConversion from Propane or Butane Gas to Natural Gas Gas Pressure Test Procedure Gas Pressure TestingSteam Information Steam Coil pH LevelWater Information Preoperational Test Preparation for Operation/Start-UpWarranty Information Service/Parts InformationPreoperational Instructions Coin ModelsRoutine Maintenance Standard Label CE Label Data Label Information07/15/08