a.The pressure of the condensate in the steam supply will cause water hammer and subsequent heat exchanger (steam coil) failure. The steam supply connection into the main supply line must be made within a minimum
b.The steam supply piping to the dryer must include a
c.Flexible hoses or couplings must be used. The dryer vibrates slightly when it runs and this will cause the steam coil connections to crack if they are hard piped to the supply and return mains.
d.
e.Install an inverted bucket steam trap and check valve for each unit at least
1)An inverted bucket steam trap with capacity of 1,400 pounds of condensate per hour @ 125 PSI is required for each dryer.
f.A 3/4" vacuum breaker should be installed. This will save energy and provide for safety of the operator and maintenance personnel.
g.The supply and return lines should be insulated. This will save energy and provide for safety of the operator and maintenance personnel.
h.Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing coil damage. ALL horizontal runs of steam supply piping should be pitched
STEAM DAMPER SYSTEM