American Dryer Corp MD-170 manual Steam Information, Steam Requirements High Pressure

Page 33

H. STEAM INFORMATION

It is your responsibility to have ALL steam plumbing connections made by a qualified professional to assure that the installation is adequate and conforms with local and state regulations or codes.

IMPORTANT: Failure to comply with the requirements stipulated in this manual can result in component failure which will VOID THE WARRANTY.

NOTE: The MDS-170 is manufactured with a pneumatic (piston) damper system which requires an external supply of clean, dry, regulated air (80 PSI ±10 PSI [552 kPa ± 0.69 kPa]). Refer to Steam Damper Air System Connections, Section H, item 3.

1.Steam Coil PH Level

The normal PH level for copper type steam coils must be maintained between a value of 8.5 to 9.5. For steel type steam coils the PH level must be maintained between a value of 9.5 to 10.5. These limits are set to limit the acid attack of the steam coils.

IMPORTANT: Coil failure due to improper PH level will VOID THE WARRANTY.

2.Steam Requirements - High Pressure

Inlet ----- 1-1/2" (3.81 cm) supply line connection -- qty. one (1) at top manifold. Return -- 1-1/2" (3.81 cm) return line connection --- qty. one (1) at bottom manifold.

OPERATING STEAM PRESSURE

MAXIMUM

125 psig

862 kPa

 

 

 

MINIMUM

100 psig*

689 kPa

 

 

 

HEAT INPUT (Normal Load)

19 Bhp

 

 

 

CONSUMPTION (Approximate) @ 125 PSI

725 lbs/hr

329.1 kg/hr

 

 

 

Shaded areas are stated in metric equivalents

*Minimum operating pressure for optimium results.

3.Installation Instructions

To insure that an adequate supply of steam is provided, be sure that the steam supply and steam return lines are sized and laid out as stipulated in this manual. Inadequate steam supply and steam return lines or improper steam plumbing will result in poor performance and can cause component failure. Clean, dry, regulated steam must be provided to the dryer.

IMPORTANT: Steam coil failure due to water hammer by wet steam will VOID THE WARRANTY.

29

Image 33
Contents Maytag Co MD-170 Installation/Operators ManualRetain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsGAS Supply or the Steam Supply Before ANY Covers or Specifications GAS and Steam Specifications / Component IdentificationSpecifications MDG-170 Gas MDS-170 Steam Component Identification Page Location Requirements Installation ProceduresUNPACKING/SETTING UP Round duct can now be connected to the dryer Dryer Enclosure Requirements Fresh AIR Supply Create a Potential Fire Hazard Exhaust RequirementsPage Page Page Page Page Electrical Information MDG-170 Gas MDS-170 Steam Page Page GAS Information Type of GAS Latest Edition Page Steam Requirements High Pressure Steam InformationSteam Damper System 621 kPa DiagramPage Preparation for OPERATION/START-UP Switch Otherwise the Dryer will not StartPreoperational Tests Natural Gas Inches W.C .5 millibars Basket Coating Shut Down Instructions621 kPa Compressed AIR RequirementsSERVICE/PARTS Information ServiceParts Returning Warranty Cards Warranty InformationRoutine Maintenance CleaningClean the lint drawer or screen every third or fourth load Createa Potentialfire Hazard Lubrication AdjustmentsDrive motor is not operating does not start TroubleshootingFailed blower impellor/fan drive shaft bearings Blower impellor/fan motor is not operating does not startFailed microprocessor controller computer Failed keyboard touchpad label assembly GAS Models Steam Models Dryer operates but is taking too long to dry Gas Models Condensation on main door glass AA. Excessive noise and/or vibration Dryer or scraping noise at tumbler basket areaFailed drive motor contactor relay Failed motor Failed blower impellor/fan drive shaft bearings Steam Models Gas Models Steam Models Condensation on main door glass Excessive noise and/or vibration Timing Legend Reversing Timer SPIN/DWELLADJUSTMENTSData Label Location / Information GAS Manifold Pressure for GAS Dryers Data LabelMicroprocessor computer Board Procedure for Functional Check Replacement ComponentsModels manufactured with ADC module Part No Theory Of Operation P O R T a N T ADC P/N114501 02/16/00-25 2- 02/25/00-250