American Dryer Corp ADH-75, ADH-170 Dryer Enclosure Requirements, Fresh Air Supply Requirements

Page 17

Dryer Enclosure Requirements _______

Bulkheads and partitions should be made of noncombustible material.

Note

!Allowances must be made for opening the control door.

AThe optimum opening of load door is 30-inches (76.2 cm) for ADH-75; and 38-1/4” (76.2 cm) for ADH-120 and ADH-170.

BThe maximum thickness of the bulkhead is 4-inches (10.16 cm). For electric dryers the maximum thickness of the bulkhead is 1-inch (2.54 cm) within 3-inches (7.62 cm) from the top of the control door.

CFor electric dryers a minimum overhead clearance of 12-inches (30.48 cm) is required, providing no sprinkler is located above the dryer. For steam dryers or if a sprinkler is located above the dryer, 18-inches (45.72 cm) is required.

DDryer should be positioned 12-inches (30.48 cm) for ADH-75; 24-inches (60.96 cm) for ADH-120 and ADH-170, away from the nearest obstruction and 24-inches (60.96 cm) for ADH-75; 36-inches (91.44 cm) for ADH-120 and ADH-170 is recommended for ease of installation, maintenance, and service.

EFlush to the opening of the control door.

FFlooring should be level or below dryer cabinet for ease of removing panels during maintenance.

GDryers may be positioned sidewall to sidewall, however a 1/16” (1.5875 mm) minimum allowance must be made for the opening and closing of the control door, along with the removal of panels during maintenance.

Fresh Air Supply Requirements _______

When the dryer is operating, it draws in room air, heats it, passes this air through the tumbler, and exhausts it out of the building. Therefore, the room air must be continually replenished from the outdoors. If the make-up air is inadequate, drying time and drying efficiency will be adversely affected. Ignition problems and sail switch “fluttering” problems may result, as well as premature motor failure from overheating. The dryer must be installed with provisions for adequate combustion and make-up air supply.

Air supply (make-up air) must be given careful consideration to ensure proper performance of each dryer. As a general rule, an unrestricted air entrance from the outdoors (atmosphere) of a minimum of 1-1/2 square feet (0.14 square meters) ADH-75; 3 square feet (0.28 square meters) ADH-120; 4 square feet (0.37 square meters) ADH-170; is required for each dryer.

ADH-75

A = 2 ft (0.61 m)

B = 18” (45.72 cm)

ADH-120

A = 2 ft (0.61 m)

B = 3 ft (0.91 m)

ADH-170

A = 3 ft (0.91 m)

B = 3 ft (0.91 m)

To compensate for the use of registers or louvers used over the openings, this area must be increased by approximately thirty-three percent (33%). Make-up air openings should not be located in an area directly near where exhaust vents exit the building.

It is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to all the dryers.

ADH-120 EXAMPLE: For a bank of 4 dryers, 2 unrestricted openings measuring 2 feet by 3 feet (0.61 meters by 0.91 meters) are acceptable.

Allowances must be made for remote or constricting passageways or where dryers are located at excessive altitudes or predominantly low pressure areas.

Important

!Make-up air must be provided from a source free of dry cleaning solvent fumes. Make-up air that is

contaminated by dry cleaning solvent fumes will result in irreparable damage to the motors and other dryer components.

Note

!Component failure due to dry cleaning solvent fumes will void the warranty.

113247 - 3

www.amdry.com

17

Image 17
Contents American Dryer Corporation Installation ManualRetain This Manual in a Safe Place for Future Reference Table of Contents What To Do If You Smell Gas Safety Precautions54.61 cm ADH-75 SpecificationsADEH-75 Hepa Filter Dryer ADH-120 Specifications ADEH-120 Hepa Filter Dryer ADSH-120 Hepa Filter Dryer ADSH-120 Component Identification Front View ADSH-120 Component Identification Rear View 79.69 cm ADH-170 SpecificationsADSH-170 Hepa Filter Dryer ADSH-170 Component Identification Front View ADSH-170 Component Identification Rear View Unpacking/Setting Up Installation ProceduresLocation Requirements Leveling Dryer ADH-75Fresh Air Supply Requirements Dryer Enclosure RequirementsSingle Dryer Venting Exhaust RequirementsOutside Ductwork Protection Vertical Venting Horizontal VentingADH-75 Multiple Dryer Common VentingADH-120 ADH-170Electrical Information ADEH-120 Electric Models Only ADEH-75 Electric Models OnlyADEH-170 Electric Models Only GroundingElectrical Connections Single-Phase 1ø ADSH-75 Only Wiring Connections/HookupSteam Models Only For 110V ApplicationsElectrically Heated Models Only Phase 3ø Wiring Connections/HookupFor 208-240V Applications Steam Requirements High Pressure Steam InformationSteam Coil pH Level Steam Damper System Operation Adjustment ADSH-120 Only Installation InstructionsSteam Damper Air System Connections Air RequirementsSteam Damper System Operation Filter Replacement Hepa Pressure Gauge/Alarm AddendumFilter Information ADH-75, ADH-170Preoperational Test Preparation for Operation/Start-UpPreoperational Instructions Mechanical TimerNon-Coin Models Shutdown InstructionsWarranty Information Service/Parts InformationRoutine Maintenance Data Label Information Procedure for Functional Check Replacement ComponentsDoor Interlock Manual Reset Burner Hi-Limit InstructionsHigh Temperature Alarm 113247 ADC Part No 08/15/07