American Dryer Corp ADH-75 installation manual Multiple Dryer Common Venting, ADH-120, ADH-170

Page 20

Multiple Dryer (Common) Venting

Important

!For extended ductwork runs, the cross section area of the ductwork can only be increased to an extent.

When the ductwork approaches the maximum limits as noted in this manual, a professional HVAC firm should be consulted for proper venting information.

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main duct at an angle not more than 45º in the direction of airflow. The main duct should be tapered, with the diameter increasing before each individual duct is added. The minimum diameter of the individual ductwork must be at least Dimension A (12-inches [30.48 cm] for the ADH-75; 18-inches [45.72 cm] for the ADH-120; 20-inches [50.8 cm] for the ADH-170).

The illustration on the right shows the minimum cross- sectional area for multiple dryer round or square venting. These figures must be increased if the main duct run from the last dryer to where it exhausts to the outdoors is longer than Dimension B (20 feet [6.096 meters]) or has more than 1 elbow in it.

ADH-75

Multiple Dryer Venting with 12-Inch (30.48 cm) Diameter

1,200 cfm (33.98 cmm) Exhaust Connections at Common Duct

NUMBER OF DRYERS

4

3

2

1

MINIMUM CROSS-

SQ IN

315

254

200

115

SECTIONAL AREA

SQ CM

2032

1638

1290

729

MINIMUM ROUND

IN

20

18

16

12

DUCT DIAMETER

CM

51

46

41

30

ADH-120

Multiple Dryer Venting with 18-Inch (45.72 cm) Diameter

2,500 cfm (70.79 cmm) Exhaust Connections at Common Duct

NUMBER OF DRYERS

4

3

2

1

MINIMUM CROSS-

SQ IN

455

380

255

115

SECTIONAL AREA

SQ CM

2935

2452

1645

742

MINIMUM ROUND

IN

24

22

20

18

DUCT DIAMETER

CM

61

56

51

46

Important

!ADH-75 and ADH-120: No more than 4 dryers should be connected to 1 main common duct.

ADH-170

Multiple Dryer Venting with 20-Inch (50.8 cm) Diameter

4,400 cfm (124.59 cmm) Exhaust Connections at Common Duct

NUMBER OF DRYERS

3

2

1

MINIMUM CROSS-

SQ IN

707

531

315

SECTIONAL AREA

SQ CM

4561

3426

2032

MINIMUM ROUND

IN

30

26

20

DUCT DIAMETER

CM

76

66

51

Important

!ADH-170: No more than 3 dryers should be connected to 1 main common duct.

NOTE 1 Opening must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct must be centered within this opening.

NOTE 2 Distance should be 2 times the diameter of the duct to the nearest obstruction.

NOTES ______________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

_____________________________________________________________

20

American Dryer Corp.

113247 - 3

Image 20
Contents Installation Manual American Dryer CorporationRetain This Manual in a Safe Place for Future Reference Table of Contents Safety Precautions What To Do If You Smell GasADH-75 Specifications 54.61 cmADEH-75 Hepa Filter Dryer ADH-120 Specifications ADEH-120 Hepa Filter Dryer ADSH-120 Hepa Filter Dryer ADSH-120 Component Identification Front View ADSH-120 Component Identification Rear View ADH-170 Specifications 79.69 cmADSH-170 Hepa Filter Dryer ADSH-170 Component Identification Front View ADSH-170 Component Identification Rear View Installation Procedures Unpacking/Setting UpLocation Requirements Leveling Dryer ADH-75 Dryer Enclosure Requirements Fresh Air Supply RequirementsSingle Dryer Venting Exhaust RequirementsOutside Ductwork Protection Horizontal Venting Vertical VentingMultiple Dryer Common Venting ADH-75ADH-120 ADH-170Electrical Information ADEH-75 Electric Models Only ADEH-120 Electric Models OnlyADEH-170 Electric Models Only GroundingSingle-Phase 1ø ADSH-75 Only Wiring Connections/Hookup Electrical ConnectionsSteam Models Only For 110V ApplicationsElectrically Heated Models Only Phase 3ø Wiring Connections/HookupFor 208-240V Applications Steam Requirements High Pressure Steam InformationSteam Coil pH Level Installation Instructions Steam Damper System Operation Adjustment ADSH-120 OnlySteam Damper Air System Connections Air RequirementsSteam Damper System Operation Hepa Pressure Gauge/Alarm Addendum Filter ReplacementFilter Information ADH-75, ADH-170Preparation for Operation/Start-Up Preoperational TestMechanical Timer Preoperational InstructionsNon-Coin Models Shutdown InstructionsService/Parts Information Warranty InformationRoutine Maintenance Procedure for Functional Check Replacement Components Data Label InformationDoor Interlock Manual Reset Burner Hi-Limit InstructionsHigh Temperature Alarm 113247 ADC Part No 08/15/07