E. EXHAUST REQUIREMENTS

1.General Exhaust Duct Work Information

Exhaust duct work should be designed and installed by a qualified professional. Improperly sized duct work will create excessive back pressure which results in slow drying, increased use of energy, overheating of the dryer, and shutdown of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler) hi-heat thermostats.

CAUTION: DRYER MUST BE EXHAUSTED TO THE OUTDOORS.

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCT WORK CAN CREATE A POTENTIAL FIRE HAZARD.

The duct work should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns as possible. Single or independent dryer venting is recommended.

HORIZONTAL VENTING:

When single dryer venting is used, the length of duct work, from the dryer to the outside exhaust outlet, should not exceed fifteen (15) feet. The minimum diameter of this duct work must be at least 10-inches (even though the dryer exhaust duct is only 8-inches). In the case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust outlet should not exceed fifteen (15) feet. The shape of the duct work is not critical so long as the minimum cross-sectional area is provided. It is suggested that the use of 90° turns be avoided; use 30° or 45° angles instead. The radius of the elbows should preferably be 1-1/2 times the diameter of the duct. Including basket (tumbler)/dryer elbow connections or elbows used for outside protection from the weather, no more than two (2) elbows should be used in the exhaust duct run. If more than two (2) elbows are used, the cross sectional area of the duct work must be increased. ALL duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Inspection doors should be installed at strategic points in the exhaust duct work for periodic inspection and clean-out of lint from the duct work.

VERTICAL VENTING:

When single dryer venting is used the length of the duct work from the dryer to the outside exhaust outlet should not exceed twenty (20) feet. The minimum diameter of this duct work must be at least 12-inches (even though the dryer exhaust duct is only 8-inches) In the case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust outlet should not exceed twenty (20) feet. The shape of the duct work is not so critical so long as the minimum cross sectional area is provided. It is suggested that the use of 90º turns be avoided; use 30º or 45º bends instead. The radius of the elbows should preferably be 1-1/2 times the diameter of the duct. ALL duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Inspection doors should be installed at strategic points in the exhaust duct work for periodic inspection and clean-out of lint from the duct work.

IMPORTANT: Exhaust back pressure measured by a manometer in the exhaust duct should not exceed 0.3-inches of water column.

IMPORTANT: Minimum duct work diameter for horizontal venting is 10-inches and for vertical venting the minimum is 12-inches.

14

Image 18
Contents MDG-75 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement Section Important InformationSafety Precautions What to do if YOU Smell GASPage SPECIFICATIONS/COMPONENT Identification SpecificationsSpecifications Component Identification Dryer Rear View Illus. No Installation Procedures Location RequirementsUNPACKING/SETTING UP Dryer Enclosure Requirements Fresh AIR Supply Exhaust Requirements Not be Reduced Anywhere Down Stream of the Dryer Page Page Electrical Information MDG-75 GAS Page 3+$6 ‘ /&75,&$/&211&7,216/$6 Page Page GAS Information 48, 3523$1 Page Page Preparation for OPERATION/START-UP Preoperational Tests Gas DryersPage Preoperational Instructions Shut Down Instructions SERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsRoutine Maintenance CleaningDays Adjustments Days After Installation and Every 6 Months ThereafterProcedure for Functional Check Replacement Components Page Page Reversing Timer Spin and Dwell Adjustments 1* /*1’Technical Information Data LabelApplicable Approval Seals Troubleshooting From the Machine Toallowaccess for CLEANING,ADJUSTING70 3$ Microprocessor Computer Models Blower and Fan motor is not operating does not start Loose connection in main door switch circuit Page GAS Models Failed microprocessor controller computer Dryer operates but is taking too long to dry Page AA. Condensation on main door glass Timer Models Blower/Fan motor is not operating does not start Page Dryer operates but is taking too long to dry Page Condensation on main door glass Page 01/07/998-50