American Dryer Corp MLG32PDB installation manual Type of GAS

Page 24

2. Technical Gas Data

a. Gas Specifications

 

TYPE OF GAS

 

NATURAL

LIQUID PROPANE

 

 

 

Manifold Pressure*

3.5 inches W.C.

10.5 inches W.C.

 

 

 

In-Line Pressure

6.0 - 12.0 inches W.C.

11.0 inches W.C.

 

 

 

Orifice Size**

#18

#38

 

 

 

*Measured at gas valve pressure tap when the gas valve is on.

**For elevations up to 2,000 feet.

W.C. = Water column in inches.

Gas Inlet Size

3/4” N.P.T.

 

 

Btu/hr Input (Each Basket [Tumbler])

80,000

 

 

Btu/hr (Total For Both Baskets [Tumblers])

160,000

 

 

N.P.T. = National Pipe Thread.

b.Natural Gas

Regulation is controlled by each gas valve’s internal regulator. Incoming supply pressure must be consistent between a minimum of 6.0 inches and a maximum of 12.0 inches water column (W.C.) pressure.

c.Liquid Propane (L.P.) Gas

Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so that the gas pressure must be regulated upstream of the dryer. The pressure measured at each gas valve pressure tap must be a consistent 10.5 inches water column. There is no regulator or regulation provided in an L.P. dryer. The water column pressure must be regulated at the source (L.P. tank) or an external regulator must be added to each dryer.

3.Piping Connections

ALL components/materials must conform to National Fuel Gas Code Specifications ANSI Z223.1-LATEST EDITION, or in Canada, CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-M91 (L.P. Gas) or LATEST EDITION (for General Installation and Gas Plumbing), as well as local codes and ordinances and must be done by a qualified professional. It is important that gas pressure regulators meet applicable pressure requirements, and that gas meters be rated for the total amount of ALL the appliance BTUs being supplied.

The dryer is provided with a 3/4” N.P.T. inlet pipe connection at the upper right hand corner (when viewed from the rear) of each dryer. It is recommended that a gas shutoff valve be provided to the gas supply line of each dryer for ease of servicing.

20

Maytag Co.

113062 - 16

Image 24
Contents MLG32PDB Installation Manual Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Warranty Information Important Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASMaytag Co Specifications SpecificationsSpecifications Installation Procedures UNPACKING/SETTING UPLocation of the Dryer Maytag Co Dryer Enclosure Requirements Fresh AIR Supply RequirementsMaytag Co Exhaust Requirements Gauge 0.0195-inches 0.50 mm thick Maytag Co 113062 Maytag Co Electrical Information Electrical Requirements Single-Phase 1Ø Electrical Connection Leads Electrical Service Specifications PER Tumbler GAS Information Type of GAS Maytag Co Preparation for Operation Preoperational TestsNatural Gas Inches Water Column Liquid Propane L.P. Gas Shutdown Instructions Basket Tumbler CoatingOperating Instructions Starting the DryerSERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsWarranty Routine Maintenance CleaningSuggested Cleaning Schedule Adjustments LubricationDryer Data Label Information Data Label LocationData Label 16 08/08/08