Page 30

2.Technical Gas Data a. Gas Specifications

 

TYPE OF GAS

 

 

NATURAL

LIQUID PROPANE

 

 

 

 

 

Manifold Pressure*

3.5 inches W.C.

8.7 mb

10.5 inches W.C.

26.1 mb

 

 

 

 

 

In-Line Pressure

6.0 - 12.0 inches W.C.

14.92 - 29.9 mb

11.0 inches W.C.

27.4 mb

 

 

 

 

 

Shaded areas are stated in metric equivalents

* Measured at outlet side of gas valve pressure tap when gas valve is on.

b. Gas Connections

 

Inlet connection -------------------

3/4” N.P.T.

Inlet supply size -------------------

3/4” N.P.T. (minimum)

Btu/hr input (per dryer) ----------

175,000 (44,100 kcal/hr)

1)Natural Gas

Regulation is controlled by the dryer’s gas valve’s internal regulator. Incoming supply pressure must be consistent between a minimum of 6.0 inches (14.92 mb) and a maximum of 12.0 inches (29.9 mb) water column (W.C.) pressure.

2)Liquid Propane (L.P.) Gas

Dryers made for use with L.P. gas have the gas valve’s internal pressure regulator blocked open so that the gas pressure must be regulated upstream of the dryer. The pressure measured at each gas valve pressure tap must be a consistent 10.5 inches (26.1 mb) water column. There is no regulator or regulation provided in an L.P. dryer. The water column pressure must be regulated at the source (L.P. tank) or an external regulator must be added to each dryer.

 

 

 

 

TYPE OF GAS

 

Liquid Propane

 

BTU

 

 

Natural

 

 

Liquid Propane

MODEL

kcal/hr

 

 

 

Conversion Kit

Per Hour

 

 

 

Part

 

 

Part

NUMBER

Rating

Qty.

D.M.S.*

 

Qty.

D.M.S.*

Part Number

Rating

 

 

 

 

 

 

Number

 

 

Number

 

MDG75V

175,000

44,100

4

#30

 

140819

4

#49

140803

883329

 

 

 

 

 

 

 

 

 

 

 

Shaded area is stated in metric equivalent

* Drill Material Size (D.M.S.) equivalents are as follows:

Natural Gas

#30 = 0.1285” (3.2639 mm).

L.P. Gas

#49 = 0.0730” (1.8542 mm).

26

Image 30
Contents MDG75V Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement Important Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASPage Specifications SpecificationsMDG75V Component Identification Page Installation Procedures Location RequirementsUNPACKING/SETTING UP Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements General Exhaust Ductwork InformationPage Page Multiple common Dryer Venting Importantventingreminders Electrical Information Electrical RequirementsMust be Provided SINGLE-PHASE 1Ø Electrical Connections Leads Important a Circuit Servicing Each Dryer Must be Provided Page MDG75V GAS GAS Information Type of GAS Page Page Preparation for OPERATION/START-UP Preoperational Tests GAS Models onlyBasket Tumbler Coating Preoperational Instructions Shutdown InstructionsSERVICE/PARTS Information ServiceParts Routine Maintenance CleaningSuggested Cleaning Schedule Adjustments LubricationLint Drawer Removal Troubleshooting Microprocessor Controller Computer ModelsBlower motor is not operating does not start Microprocessor controller computer display reads dSFL GAS Models only Dryer operates but is taking too long to dry Dryer is making scraping noise at basket tumbler area Data Label Information Data LabelSerial Number Procedure for Functional Check Replacement Components SectionviiiPage 113160 1 11/27/02-25