American Dryer Corp MLG31PCA installation manual

Page 20

3.Multiple Dryer (Common) Venting

If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main duct at an angle not more than 45º in the direction of airflow. The main duct should be tapered, with the diameter increasing before each individual 10-inch (25.4 cm) duct (when dryer common exhaust is used) is added. If single 6-inch (15.24 cm) basket (tumbler) exhaust ducts are used, the diameter should be increased after every second 6-inch (15.24 cm) duct.

IMPORTANT: No more than four (4) dryers or eight (8) baskets (tumblers) total should be connected to one (1) main common duct.

NOTE: Refer to the illustrations on page 18 for examples of multiple dryer (common) venting.

The main duct may be any shape or cross-sectional area so long as the minimum cross-sectional area is provided. The illustrations on page 18 show the minimum cross-sectional area for multiple dryer venting. These figures must be increased in proportion if the main duct run from the last dryer to where it exhausts to the outdoors is unusually long (over 15 feet [4.57 meters]) or has numerous elbows (more than one [1]) in it. In calculating ductwork size, the cross-sectional area of a square or rectangular duct must be increased twenty percent (20%) for each additional 15 feet (4.57 meters). The diameter of a round exhaust must be increased ten percent (10%) for each additional 15 feet (4.57 meters).

IMPORTANT: For extended ductwork runs, the cross-sectional area of the ductwork can only be increased to an extent. Maximum proportional ductwork run cannot exceed 15 feet (4.57 meters) more than the original limitations of 15 feet (4.57 meters) with two (2) elbows. When the ductwork approaches the maximum limits as noted in this manual, a professional heating, venting, and air conditioning (HVAC) firm should be consulted for proper venting information.

IMPORTANT: Exhaust back pressure measured by a manometer at each basket (tumbler) exhaust duct area must be no less than 0 and must not exceed 0.3 inches (0.74 mb) water column (W.C.).

The ductwork should be smooth inside with no projections from sheet metal screws or other obstructions, which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL ductwork joints must be taped to prevent moisture and lint from escaping into the building. Also, inspection doors should be installed at strategic points in the exhaust ductwork for periodic inspection and cleaning.

NOTE: When the exhaust ductwork passes through a wall, ceiling, or roof made of combustible materials, the opening must be 2-inches (5.08 cm) larger than the duct (all the way around). The duct must be centered within this opening.

16

Image 20
Contents MLG31PCA Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement Important Information Receiving and HandlingSafety Precautions What to do if YOU Smell GASPage Specifications 71-1/2Gas Location of the Dryer Installation ProceduresUNPACKING/SETTING UP Page Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Page Page Page Page Page Electrical Information Electrical RequirementsLG31PCA GAS Information Type of GAS Typical GAS Connections Page Page Preparation for Operation Preoperational TestsPage Basket Tumbler Coating Shut Down Instructions Operating Instructions Starting the DryerPage Page Parts SERVICE/PARTS InformationService Warranty Warranty InformationReturning Warranty Cards Suggested Cleaning Schedule Routine MaintenanceCleaning Adjustments LubricationTroubleshooting SectionviiiFailed motor contactor/relay DMC computer L.E.D. display reads dSFL Failed keyboard touch pad label assembly Failed DMC computer If the dryer is equipped with optional battery back-up Dryer operates, but is taking too long to dry Condensation on main door glass Procedure for Functional Check Replacement Components Page Optional Gas Piping Kit Part No 1 02/11/02-20 05/01/02-250