D. FRESH AIR SUPPLY REQUIREMENTS

Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An unrestricted source of 800 cfm (22.65 cmm) is necessary for each dryer. An unrestricted air entrance from the outdoors (atmosphere) of a minimum of 1-1/2 square feet (0.14 square meters) is required for each dryer. This area must be enlarged if louvers or registers cover the opening. It is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the make-up air is distributed equally to the dryers. For example, for a bank of eight

(8)dryers, a total make-up air opening of 12 square feet (1.15 square meters) is required. Two (2) openings measuring 2 feet by 3 feet (6 square feet) - 0.61 meters by 0.91 meters (0.56 square meters) are acceptable. The dryer must be installed with provisions for adequate combustion and make-up air supply.

Allowances must be made for remote or constricting passageways or where dryers are located at excessive altitudes or predominantly low-pressure areas.

IMPORTANT: Make-up air must be provided from a source free of dry cleaning solvent fumes. Make-up air that is contaminated by dry cleaning solvent fumes will result in irreparable damage to the motors and other dryer components.

IMPORTANT: Make-up air openings should not be located near ductwork exhaust outlets. If make-up air openings are too close to the exhaust outlet, lint and fumes may be drawn back into the dryer area through these openings.

NOTE: Component failure due to dry cleaning solvent fumes will VOID THE WARRANTY.

11

Image 15
Contents MLG31PCA Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement Receiving and Handling Important InformationWhat to do if YOU Smell GAS Safety PrecautionsPage 71-1/2 SpecificationsGas Installation Procedures UNPACKING/SETTING UP Location of the Dryer Page Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Page Page Page Page Page Page Electrical Requirements Electrical InformationLG31PCA GAS Information Type of GAS Typical GAS Connections Page Page Preoperational Tests Preparation for OperationPage Basket Tumbler Coating Shut Down Instructions Starting the Dryer Operating InstructionsPage Page SERVICE/PARTS Information ServiceParts Warranty Information Returning Warranty CardsWarranty Routine Maintenance CleaningSuggested Cleaning Schedule Lubrication AdjustmentsSectionviii TroubleshootingFailed motor contactor/relay DMC computer L.E.D. display reads dSFL Failed keyboard touch pad label assembly Failed DMC computer If the dryer is equipped with optional battery back-up Dryer operates, but is taking too long to dry Condensation on main door glass Procedure for Functional Check Replacement Components Page Optional Gas Piping Kit Part No 1 02/11/02-20 05/01/02-250