Amana W10150612A Wire connection Power Supply Cord, Style 2 Direct wire strain relief

Page 7

Put power supply cord through the strain relief. Be sure that the wire insulation on the power supply cord is inside the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Do not further tighten strain relief screws at this point.

Style 2: Direct wire strain relief

Unscrew the removable conduit connector and any screws from a ³⁄₄" (1.9 cm) UL listed strain relief (UL marking on strain relief). Put the threaded section of the strain relief through the hole below the terminal block opening. Reaching inside the terminal block opening, screw the removable conduit connector onto the strain relief threads.

A

B

Electrical Connection Options

If your home has:

And you will be

Go to Section

 

connecting to:

 

4-wire receptacle

A UL listed,

4-wire connection:

(NEMA Type 14-30R)

120/240-volt

Power supply cord

 

minimum,

 

 

 

30-amp, dryer

 

 

power supply

 

 

cord*

 

4-wire direct

A fused

4-wire connection:

 

disconnect or

Direct Wire

 

circuit breaker

 

 

5"

box*

 

(12.7 cm)

 

 

3-wire receptacle

A UL listed,

3-wire connection:

(NEMA type 10-30R)

120/240-volt

Power supply cord

 

minimum,

 

 

 

30-amp, dryer

 

 

power supply

 

 

cord*

 

3-wire direct

A fused

3-wire connection:

 

disconnect or

Direct Wire

 

circuit breaker

 

 

3¹⁄₂"

box*

 

 

 

(8.9 cm)

 

 

*If local codes do not permit the connection of a cabinet-ground conductor to the neutral wire, go to “Optional 3-wire connection” section.

C

A. Removable conduit connector

B. Hole below terminal block opening

C. Strain relief threads

Put direct wire cable through the strain relief. The strain relief should have a tight fit with the dryer cabinet and be in a horizontal position. Tighten strain relief screw against the direct wire cable.

4.Now complete installation following instructions for your type of electrical connection:

4-wire(recommended)

3-wire(if 4-wire is not available)

4-wire connection: Power Supply Cord

IMPORTANT: A 4-wire connection is required for mobile homes and where local codes do not permit the use of 3-wire connections.

BF

A

C D EG

A.4-wire receptacle (NEMA type 14-30R)

B.4-prong plug

C.Ground prong

D.Neutral prong

E.Spade terminals with upturned ends

F. ¾" (1.9 cm) UL listed strain relief

G. Ring terminals

7

Image 7
Contents 29 73.7 CM Electric Dryer Installation Instructions Parts needed Tools and PartsLocation Requirements Parts suppliedIt is your responsibility Installation ClearancesMobile Home Additional Installation Requirements Electrical Requirements U.S.AElectrical Connection If connecting by direct wireIf your outlet looks like this Canada Electrical Requirements CanadaElectrical Connection U.S.A. Only Power Supply Cord Direct WireInstall strain relief Style 1 Power supply cord strain reliefStyle 2 Direct wire strain relief Wire connection Power Supply CordRemove center silver-colored terminal block screw Wire connection Direct WireBDE CG F Optional 3-wire connection Venting Requirements If using an existing vent systemIf this is a new vent system Vent material Plan Vent System Special provisions for mobile home installationsDetermine vent path Level Dryer Install Vent SystemInstall Leveling Legs Vent system chartReversible Large Side-Swing Door Reverse Door Swing OptionalReversible Super Wide Side-Swing Door If the dryer will not start, check the following Complete InstallationU.S.A CanadaPièces fournies Outillage et piècesPièces nécessaires On a besoin de Exigences d’emplacementDimensions de la sécheuse Dégagements de séparation à respecterSpécifications électriques- Canada ’installation dans une maison mobile exige’est à l’utilisateur qu’incombe la responsabilité de En cas dutilisation du système dévacuation existant Exigences concernant lévacuationLe clapet incliné de type boîte ci-dessous est acceptable Planification du système d’évacuationUne réduction de la longévité de la sécheuse Installation du système d’évacuationInstallation des pieds de nivellement Déterminer litinéraire dacheminement du conduitGrande porte réversible à pivotement latéral Mise à niveau de la sécheuseRaccordement du conduit d’évacuation Inversion du sens douverture de la porte FacultatifSi la sécheuse ne démarre pas, vérifier ce qui suit Achever l’installationTous droits réservés W10150612A SP PN W10150613A