American Dryer Corp AD-310 Phase 7 service manual First Visual Check

Page 24

h. Troubleshooting Flow Chart - Quick Reference...

First Visual Check

No Spark And System Does Not Work

Is power available

to primary?

No

Yes

 

 

 

Determine why

voltage is not present.

Is 24 VAC available at transformer?

No

Yes

Replace

Transformer.

Reset

or replace hi-limits

Is 24 VAC present from terminal

THS(2) to ground?

No

Yes

Are thermostat contacts and hi-limit control contacts closed?

No

Yes

Check continuity of wiring to determine why voltage does not exist at THS(2).

Is jumper installed from terminal 5 to ground?

Install

 

 

 

 

 

 

No

Yes

Jumper.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Open thermostat contacts for 30 seconds.

Close contacts and wait for prepurge (if applicable)

period. Is spark present now?

No

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn off supply voltage.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Check high voltage cable.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is it securely attached

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to DSI module?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is condition of high voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cable good (not brittle,

 

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

burnt, or cracked)?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Securely attach wire

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

to DSI module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace high

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

voltage cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Is spark electrode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ceramic cracked

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or is electrode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

grounded out?

 

 

 

 

 

 

 

 

 

Replace

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

 

Yes

 

 

 

 

 

 

 

 

 

DSI module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Replace spark electrode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

assembly.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System was in lockout.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Observe a complete operating

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

cycle to determine why

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

control locked out.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 0

Image 24
Contents AD-310 Phase Retain This Manual In a Safe Place For Future Reference Important Note to PurchaserFor Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement AD-310 Reference Guide Base Section Section Explosion could ResultStandards Cleaning LiquidsAT 80 PSI 5.51 Bars Lubrication Every 3 MonthsAdjustments Days After Installation and Every 6 Months ThereafterSpecifications and Dimensions Dimensions Obligation Obligation Installation Requirements ENCLOSURE/AIR SUPPLY/EXHAUST RequirementsOperational Service Check Procedure Electrical and GAS RequirementsHeat Section Direct Spark Ignition DSI System COMPONENTS/FUNCTIONSVAC Direct Spark Ignition DSI Modules 225º F 107º C Thermostat Redundant Gas Valve First Visual Check Second Visual Check Third Visual Check Troubleshooting the Direct Spark Ignition DSI System ManometerPage Page Page First Visual Check Second Visual Check Third Visual Check With a Flame DSI Ignitor/Flame-Probe Assembly Adjustments Page Flash Green Continuously Page With a Flame DSI Ignitor/Flame-Probe Assembly Adjustments Page Light RED Continuously Page Createapotentialsafety Hazard Made of Brass and can be Easily DamagedSteam Coil System Operation General OverviewPage Page Page Page Sprinkler System Description MAN3488 Page Supplies Before Servicing the Dryer Page Page Tilting System Description Page Page Page Page Page AIR JET Assembly Page Blower Squirrel Cage Fan Motor Assembly Page Page Important do not Overtighten V-BELTS Important do not Overtighten V-BELTS Page Page FILTER/REGULATOR Assembly Regulator OperationDoor Systems Manual Doors Automatic Doors Page Page Page Control and Electrical System Ladder Diagram Page Button does not Disable the High Voltage to the Dryer Page ºC + ºC + ºK Page Page Page Page Page Page Tumbler/Drum SECTION. Serious Injury can Result Tumbler/Drum SECTION. Serious Injury can Result Basket Tumbler Drive System Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Page Page Important do not Overtighten Turnbuckle Page Page Page Phase 7 OPL System Diagnostics Inputs RED Outputs Green Fdrc RED L.E.D Lint RED L.E.D 100 101 Troubleshooting Drive motor is not operating does not start Impellor fan motor is not operating does not start 105 106 Dryer operates but is taking too long to dry Excessive noise and vibration 109 Procedure for Functional Check Replacement Components 111 ADC 450049 1- 09/14/00-25