6)Remove steam coil damper cylinder (piston).

7)Remove the steam coil damper by unbolting from its hinges.

8)Disconnect steam supply lines and steam return lines at the unions.

9)Remove the remaining piping from the steam coil.

10)Remove ALL of the panels surrounding the steam coil.

11)Unbolt the steam coil and remove.

WARNING: The steam coil is heavy. Acrane may be needed to remove (and install) the steam coil.

12)Remove the steam coil damper hinges from the old coil and install them on the new steam coil.

13)Hoist the new steam coil into place and bolt down.

14)Replace ALL of the panels removed in Step #10.

15)Reinstall ALL of the piping removed from the old steam coil in Step #9.

NOTE: Thread sealant certified for steam piping must be applied to the threads.

16)Reconnect ALL of the piping (supply lines and return lines) disconnected in Step #8.

17)Reinstall steam damper cylinder (piston) removed in Step #6.

18)Reestablish electrical power to the dryer.

19)Close the 1/2” (12.7 mm) plug which was opened in Step #5.

WARNING: THE 1/2” (12.7 MM) PLUG MUST BE CLOSED BEFORE ATTEMPTING TO APPLYANY STEAM PRESSURE.

20) Slowly open the return line then slowly open the supply line.

4 5

Image 49
Contents AD-310 Phase Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement AD-310 Reference Guide Base Section Explosion could Result SectionStandards Liquids CleaningAT 80 PSI 5.51 Bars Every 3 Months LubricationDays After Installation and Every 6 Months Thereafter AdjustmentsSpecifications and Dimensions Dimensions Obligation Obligation ENCLOSURE/AIR SUPPLY/EXHAUST Requirements Installation RequirementsElectrical and GAS Requirements Operational Service Check ProcedureDirect Spark Ignition DSI System COMPONENTS/FUNCTIONS Heat SectionVAC Direct Spark Ignition DSI Modules 225º F 107º C Thermostat Redundant Gas Valve First Visual Check Second Visual Check Third Visual Check Manometer Troubleshooting the Direct Spark Ignition DSI SystemPage Page Page First Visual Check Second Visual Check Third Visual Check With a Flame DSI Ignitor/Flame-Probe Assembly Adjustments Page Flash Green Continuously Page With a Flame DSI Ignitor/Flame-Probe Assembly Adjustments Page Light RED Continuously Page Made of Brass and can be Easily Damaged Createapotentialsafety HazardGeneral Overview Steam Coil System OperationPage Page Page Page Sprinkler System Description MAN3488 Page Supplies Before Servicing the Dryer Page Page Tilting System Description Page Page Page Page Page AIR JET Assembly Page Blower Squirrel Cage Fan Motor Assembly Page Page Important do not Overtighten V-BELTS Important do not Overtighten V-BELTS Page Page Regulator Operation FILTER/REGULATOR AssemblyDoor Systems Manual Doors Automatic Doors Page Page Page Control and Electrical System Ladder Diagram Page Button does not Disable the High Voltage to the Dryer Page ºC + ºC + ºK Page Page Page Page Page Page Tumbler/Drum SECTION. Serious Injury can Result Tumbler/Drum SECTION. Serious Injury can Result Basket Tumbler Drive System Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Page Page Important do not Overtighten Turnbuckle Page Page Page Phase 7 OPL System Diagnostics Inputs RED Outputs Green Fdrc RED L.E.D Lint RED L.E.D 100 101 Troubleshooting Drive motor is not operating does not start Impellor fan motor is not operating does not start 105 106 Dryer operates but is taking too long to dry Excessive noise and vibration 109 Procedure for Functional Check Replacement Components 111 ADC 450049 1- 09/14/00-25