d. Sprinkler Digital Temperature Controller

 

The sprinkler digital temperature controller is a programmable

 

microprocessor used to monitor temperatures via a Resistive

 

Temperature Device (RTD).

MAN3488

NOTE: Operating parameters are preset at the factory and should not require any adjustment.

2.Sprinkler System Operation

NOTE: Refer to the ladder diagram provided with the dryer for specific relay logic.

Master Relay - The coil in this relay must be energized in order to close the contacts needed to supply power to the dryer’s control system.

Relay 1 - The coil in this relay energizes if the set- point is reached closing Contact 1 and Contact 2. Contact 1 latches Relay 1 on. Contact 2 closes, turning on the sprinkler, the horn, and the reset button light. Relay 1 will remain energized until the reset button is pushed.

Relay 2 - The coil in this relay energizes if the set- point is reached closing Contact 3, de- energizing the Master Relay, and shutting power off to the dryer. Relay 2 will remain energized until the reset button is pushed.

NOTE: The Sprinkler System will remain on until the basket (tumbler) temperature falls below the set-point, and the reset button is manually activated.

3. Sprinkler System Component Replacement

a.RTD Replacement

1)Turn the water supply to the dryer off.

2)Discontinue electrical power to the dryer.

3)Remove the 1/4” (6.35 mm) compression fitting.

4)Remove the two (2) screws from the junction box cover.

4 7

Image 51
Contents AD-310 Phase Important Note to Purchaser Retain This Manual In a Safe Place For Future ReferenceFor Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement AD-310 Reference Guide Base Section Explosion could Result SectionStandards Liquids CleaningAT 80 PSI 5.51 Bars Every 3 Months LubricationDays After Installation and Every 6 Months Thereafter AdjustmentsSpecifications and Dimensions Dimensions Obligation Obligation ENCLOSURE/AIR SUPPLY/EXHAUST Requirements Installation RequirementsElectrical and GAS Requirements Operational Service Check ProcedureDirect Spark Ignition DSI System COMPONENTS/FUNCTIONS Heat SectionVAC Direct Spark Ignition DSI Modules 225º F 107º C Thermostat Redundant Gas Valve First Visual Check Second Visual Check Third Visual Check Manometer Troubleshooting the Direct Spark Ignition DSI SystemPage Page Page First Visual Check Second Visual Check Third Visual Check With a Flame DSI Ignitor/Flame-Probe Assembly Adjustments Page Flash Green Continuously Page With a Flame DSI Ignitor/Flame-Probe Assembly Adjustments Page Light RED Continuously Page Made of Brass and can be Easily Damaged Createapotentialsafety HazardGeneral Overview Steam Coil System OperationPage Page Page Page Sprinkler System Description MAN3488 Page Supplies Before Servicing the Dryer Page Page Tilting System Description Page Page Page Page Page AIR JET Assembly Page Blower Squirrel Cage Fan Motor Assembly Page Page Important do not Overtighten V-BELTS Important do not Overtighten V-BELTS Page Page Regulator Operation FILTER/REGULATOR AssemblyDoor Systems Manual Doors Automatic Doors Page Page Page Control and Electrical System Ladder Diagram Page Button does not Disable the High Voltage to the Dryer Page ºC + ºC + ºK Page Page Page Page Page Page Tumbler/Drum SECTION. Serious Injury can Result Tumbler/Drum SECTION. Serious Injury can Result Basket Tumbler Drive System Important do not Overtighten Turnbuckle Important do not Overtighten Turnbuckle Page Page Important do not Overtighten Turnbuckle Page Page Page Phase 7 OPL System Diagnostics Inputs RED Outputs Green Fdrc RED L.E.D Lint RED L.E.D 100 101 Troubleshooting Drive motor is not operating does not start Impellor fan motor is not operating does not start 105 106 Dryer operates but is taking too long to dry Excessive noise and vibration 109 Procedure for Functional Check Replacement Components 111 ADC 450049 1- 09/14/00-25