2.Electrical Service Specifications
MLG-460
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT: 208 VAC and 240 VAC ARE NOT THE SAME. When ordering, specify exact voltage.
exact voltage .
NOTES: A. Fuse ratings are
Circuit breakers are thermal magnetic (industrial) type ONLY. For others, calculate/verify correct breaker size according to
B.appliance
amp draw rating and type of breaker used.
C.Circuit breakers for 3Ø dryers must be
SERVICE |
| WIRE | APPROX. | MINIMUM | FUSING | CIRCUIT | ||
PHASE | AMP DRAW | |||||||
| ||||||||
VOLTAGE |
| SERVICE | 60 Hz | 50 Hz | WIRE SIZE* | Dual Element | BREAKER | |
|
|
|
| Time Delay |
| |||
|
|
|
|
|
|
| ||
208 | 3ø | 3/4 | 107 | 1/0 | 150 | 150 | ||
240 | 3ø | 3 | 104 | 109 | 1/0 | 150 | 150 | |
380 | 3ø | 3/4 | 60 | 4 | 100 | 90 | ||
|
|
|
|
|
|
|
| |
416 | 3ø | 3/4 | 57 | 4 | 90 | 90 | ||
460 | 3ø | 3/4 | 52 | 4 | 80 | 90 |
DEDICATED SPRINKLER SERVICE
Dryer
Nameplate
1ø
2
16
3.5
5
* AWG Stranded Wire Type...for individual lengths less than 100 feet (31 m).
IMPORTANT: The dryer must be connected to the electric supply shown on the data label that is affixed to the right side of the main electrical enclosure. In the case of 208 VAC or 240 VAC, the supply voltage must match the electric service specifications of the data label exactly.
WARNING: 208 VAC and 240 VAC ARE NOT THE SAME. Any damage done to the dryer components due to improper voltage will automatically VOID THE WARRANTY.
IMPORTANT: For proper sprinkler and dryer operation, sprinkler must be powered by a “separate or dedicated”
NOTE: For
NOTE: Contact the factory for electrical information not listed.
NOTE: ADC reserves the right to make changes in specifications at any time, without notice or obligation.
23