American Dryer Corp MLG-460 manual Burner Ignition, Introduction

Page 65

B. BURNER IGNITION

Introduction

The heart of the dryer’s burner control section is a burner controller module. It is located on the upper right hand side of the Main Electrical Enclosure panel and is described in detail in Section VI, Part D, Gas Burner and Ignition System on page 37 through page 45).

As noted below the burner ignition section of the dryer comprises a number of safety devices that have to be satisfied prior to burner ignition. Messages have been provided to aid one in isolating a specific area, however knowledge of the system is required to troubleshoot it.

The following information will provide means to respond to “Burner Fault Messages” and to verify ALL the signals necessary for BURNER IGNITION.

Burner Controller Input Signal Components

AC POWER TO THE BURNER CONTROLLER

PLC (Programmable Logic Controller) OUT 4 “HEAT ON”

FUSE 15

BURNER DOOR SWITCHES DSA4-A and DSA-B

LOAD DOOR SWITCH DS1B

UNLOAD DOOR SWITCH DS2-B

BURNER FAN AIR PRESSURE SWITCH PRS2

GAS HI PRESSURE and GAS LO PRESSURE SWITCHES PRS1 & PRS2

LINT CHAMBER AIR PRESSURE SWITCH

SIX (6) CHANNEL HIGH TEMPERATURE LIMIT SWITCH

STOP MOTION DETECTOR RELAY CONTACT SMD NO

FLAME DETECTOR PROBE

BURNER CHASSIS GROUND

1.Burner Section Input Circuit Component Description

NOTE: Refer to MLG-460 Ladder Diagram for reference.

AC POWER TO THE BURNER CONTROLLER

110 VAC power is supplied to the burner controller module PIN #1 through “FUSE 6.” Power is applied to this point when “MCR” (motor control relay) is closed.

PLC (Programmable Logic Controller) OUT “HEAT ON”

When this 110 VAC signal is asserted, a number of safety interlocks must be satisfied, before any burner ignition can take place. This signal is derived from the PLC OUTPUT #4 and is fused.

FUSE 15

This fuse is located on the upper left hand section of the Main Electrical Enclosure Panel, with the other PLC output fuses. Its function is to protect PLC (Programmable Logic Controller) output.

61

Image 65
Contents MLG-460 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Troubleshooting TOC Service PartsReturning Warranty Cards Parts Returning Warranty Parts Section What to do if YOU Smell GAS Safety PrecautionsPage Specifications SpecificationsSpecifications Reassembly of Dryer Installation ProceduresPage Page Location Requirements Internal AIR, Electric and Water Connections Page Page Page Page Page Left Drum Motor External Supply Connections Page Page Electrical Requirements Electrical RequirementsMLG-460 Page Fresh AIR Supply Requirements Preparation for Operation PRE START-UPCleaning Routine MaintenanceMonthly Component System Descriptions Page Page Main AIR Blower and Heat Reclaimer System Page Compressed AIR System Page Page GAS Burner and Ignition System Switch #2 Intermittent Pilot Page Page Page Page Page Page Page Safety Devices Door Open Parts ServiceReturning Warranty Parts Returning Warranty CardsWarranty Page Troubleshooting Probable Causes Power MalfunctionsPossible Solutions No Control Power Blue Light Off Machine Main Power Shuts Down Blue Indicator Off 2CRB Sprinkler Circuit Description Page Front Panel Blue Light and RED Light on Possible Solutions Unless the Water Valve to the Sprinkler is Closed General DescriptionBurner Ignition Burner Controller Input Signal ComponentsIntroduction Burner Section Input Circuit Component DescriptionLoad Door Switch DS1B Stop Detector Relay Contact SMD no Output Signal Component DescriptionGAS Fault Message gas system only Heater Fault Message Possible Solutions Page Page AIR Fault Message HI-TEMP Fault Message Possible Solutions Drum Fault Message Page Tumbler Basket Section Electrical Components Tumbler Basket Section Electrical MalfunctionsFollowing is for 2-Door Models only Rear Panel Control Problems Probable Causes Possible Solutions PLC OUT PIN 7 = Unload Door Open PLC OUT PIN 10 = Front UP Unload 1 Selection Probable CausesDoor Open Problem Drum Fault Message Malfunction Probable Causes Page Rear Down Switch LS2 Front Door SwitchLint Drawer Proximity Switches Base Section Electrical MalfunctionsProbable Solutions Lint Chamber Pressure Switch PS3Tumbler Basket Tilt Problems Level Fault Page Lint Screen Mechanism Problem Screen Fault Lint Chamber Air Pressure Problem AIR Fault Pendant Electrical Components Pendant Control MalfunctionsVerify Pendant Electrical Signals ML-460 Pendant Assembly Diagram Temperature Sensing Page Temperature Measurement and Sensing Problems Motors Circuit Wiring to the Analog Input ModuleMotor Protection Device Descriptions Motor Actuation Problems Probable CausesMotor Fault Screen FaultGAS Fault AIR Fault