INSTALLATION

1.Requirements

The fire suppression system must be supplied with a minimum water pipe size of 1/2” and be provided with 40 psi +/- 20 psi (2.75 bar +/- 1.37 bar) of pressure. For use of optional manual bypass, a second source with the same piping and pressure requirements is required.

Flexible 1/2 feeds must be provided to avoid damage to electric water solenoid valve by vibration.

IMPORTANT: Flexible supply line/coupling must be used. Solenoid valve failure due to hard plumbing connections WILLVOID WARRANTY.

If the rear area of the dryer or the water supply is located in an area where it will be exposed to cold/freezing temperatures, provisions must be made to protect these water lines from freezing.

WARNING: If the water in the supply line or water solenoid valve freezes, the fire suppression system will be INOPERATIVE!!

IMPORTANT: Appliance is to be connected to the water mains using a new hose set and the old hose set should not be reused.

2.Water Connections:

The water connection is made to the 3/4”-11.5 NH hose adaptor located at the rear upper midsection of the dryer (refer to the photograph).

The water solenoid valve has a 3/8” M.P.T. connection supplied with a 3/4”-11.5 NH hose adaptor to provide the minimum 1/2-inch supply (feed) line. Flexible supply line/coupling must be used in an effort to avoid damaging the electric water solenoid valve.

NOTE: The 3/4”-11.5 NH is a standard hose coupling screw thread. It is not to be confused with 3/4” N.P.T. The sealing of an NH connection is made with a washer opposed to the mating threads of an N.P.T. assembly. The two (2) thread designs are not compatible.

IMPORTANT: Flexible supply line/coupling must be used. Solenoid valve failure due to hard plumbing connections WILL VOID WARRANTY. It is recommended that a filter or strainer be installed in the water supply line.

30

Maytag Co.

113307 - 7

Image 34
Contents MDG30PNH / MDG30MNV Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Safety Precautions SectionStandards Specifications 13.6 kgSpecifications UNPACKING/SETTING UP Installation ProceduresLocation Requirements Dryer Enclosure Requirements Fresh AIR Supply Requirements Exhaust Requirements Single Dryer Venting Multiple Dryer Common Venting Electrical Information Electrical RequirementsService Phase Wire Approx Circuit AMP Draw Single-Phase Electrical Lead Connections GAS Information Type of GAS Maytag Co Preparation for OPERATION/START-UP Preoperational Tests GAS Models onlyDual Timer Dryers Preoperational InstructionsReversing Timer SPIN/DWELL Adjustments Shutdown InstructionsService SERVICE/PARTS InformationParts Returning Warranty Cards Warranty InformationWarranty Cleaning Routine MaintenanceSuggested Cleaning Schedule Adjustments LubricationData Label Information Procedure for Functional Check Replacement Components Maytag Co 113307 Fire Suppression System In Action Fire Suppression SystemInstallation Water ConnectionsTypical Water Supply 06/26/08