MULTIPLE DRYER (COMMON) VENTING
IMPORTANT: For extended ductwork runs, the cross section area of the ductwork can only be increased to an extent. When the ductwork approaches the maximum limits as noted in this manual, a professional heating, ventilating, and
If it is not feasible to provide separate exhaust ducts for each dryer, ducts from individual dryers may be channeled into a “common main duct.” The individual ducts should enter the bottom or side of the main duct at an angle not more than 45º in the direction of airflow. The main duct should be tapered, with the diameter increasing before each individual duct is added. The minimum diameter of the individual ductwork (Dimension A) must be at least
IMPORTANT: No more than four (4) dryers should be connected to one (1) main common duct.
The illustration below shows the minimum
For gas models Dimension B is 20 feet (6.096 meters).
Multiple Dryer Venting (Gas) with
NUMBER OF DRYERS | 4 | 3 |
| 2 |
| 1 | |||
MINIMUM CROSS- | SQ IN | 164 | 120 |
| 80 |
| 54 | ||
SECTIONAL AREA | SQ CM | 1058 | 774 |
| 516 |
| 348 | ||
MINIMUM ROUND | IN | 14 | 12 |
| 10 |
| 8 | ||
DUCT DIAMETER | CM | 35.56 | 30.48 |
| 25.4 |
| 20.32 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
NOTE 1 Opening must be