Maytag MLG32PDA manual Dryer Enclosure Requirements, Fresh AIR Supply

Page 14

C.DRYER ENCLOSURE REQUIREMENTS

Bulkheads and partitions should be made of noncombustible materials and must be located a minimum of twelve (12) inches (18-inches or more is recommended for ease of installation, maintenance , and service) above the dryer outer top, except along the front of the dryer which may be closed in if desired.

NOTE: Even though a minimum of 12-inches above the dryer outer top is acceptable, a clearance of 18-inches (or more) is suggested for ease of installation and service

(electrical power connections).

NOTE: When fire sprinkler systems are located above the dryers, a minimum of 12-inches above the dryer outer top is required.

NOTE: Allowances must be made for opening the control door.

Dryers may be positioned side wall to side wall. However, allowances must be made for opening and closing of the control door and the lint door. It is suggested that the dryer be positioned about two (2) feet away from the nearest obstruction for ease of installation, maintenance, and service (to be measured from the back guard.) (Refer to the previous illustration (on page 10) for details.)

NOTE: Air considerations are important for proper and efficient operation.

D.FRESH AIR SUPPLY

Air supply (make-up air) must be given careful consideration to assure proper performance of each dryer. An unrestricted source of 800 cfm is necessary for each dryer. An unrestricted air entrance from the outdoors (atmosphere) of a minimum of 1-1/2 square feet is required for each dryer. This area must be enlarged if louvers or registers cover the opening. It is not necessary to have a separate make-up air opening for each dryer. Common make-up air openings are acceptable. However, they must be set up in such a manner that the make up air is distributed equally to the dryers. For example, for a bank of eight (8) dryers, a total make-up air opening of 12 square feet is required. Two (2) openings measuring 2' by 3' (6 square feet) are acceptable. (Refer to the illustration on page 14.)

Allowances must be made for remote or constricting passageways or where dryers are located at excessive altitudes or predominantly low-pressure areas.

IMPORTANT: Make-up air must be provided from a source free of dry cleaning solvent fumes. Make-up air that is contaminated by dry cleaning fumes will result in irreparable damage to motors and other dryer components.

10

Image 14
Contents MLG32PDA What do YOU do if YOU Smell GASRetain This Manual In a Safe Place For Future Reference Page For Your Safety Table of Contents Routine Maintenance Section Important InformationSafety Precautions What to do if YOU Smell GASCan Create a Fire Hazard Specifications MLG32PDA Installation Procedures UNPACKING/SETTING UPLocation of the Dryer Dryer Enclosure Requirements Fresh AIR SupplyPage Exhaust Requirements Single Dryer VentingPage Page Page Electrical Information Page 120 GAS Information Type of GAS Page Preparation for Operation Preoperational TestsGas Inches Water Column Shut Down Instructions Operating Instructions Starting the DryerParts SERVICE/PARTS InformationService Warranty Warranty InformationReturning Warranty Cards Routine Maintenance CleaningDays Adjustments LubricationPart No 1 01/13/98-500 2* 05/06/98-500 05/19/98-500