E. EXHAUST REQUIREMENTS
Exhaust duct work should be designed and installed by a qualified professional. Improperly sized duct work will create excessive back pressure which results in slow drying, increased use of energy, overheating of the dryer, and shutdown of the burner by the airflow (sail) switches, burner
CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCT WORK CAN CREATE A POTENTIAL FIRE HAZARD.
The exhaust duct work should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns as possible. When single dryer venting is used, the duct work from the dryer to the outside exhaust outlet should not exceed twenty (20) feet. In the case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust outlet should not exceed twenty (20) feet. The shape of the exhaust duct work is not critical so long as the minimum
1.SINGLE DRYER VENTING
Where possible, it is suggested to provide a separate exhaust duct for each dryer. The exhaust duct work should be laid out in such a way that the duct work travels as directly as possible to the outdoors with as few turns as possible. It is suggested that the use of 90º turns in ducting be avoided; use 30º or 45º angles instead. The shape of the exhaust duct work is not critical so long as the minimum
IMPORTANT: Exhaust back pressure measured by a manometer at each basket exhaust duct area should not exceed 0.3 inches of water column.
It is suggested that the duct work from each dryer not exceed 20 feet with no more than two (2) elbows. If the duct work exceeds 20 feet or has numerous elbows, the
IMPORTANT: For extended duct work runs, the
The duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Also, inspection doorsshould be installed at strategic points in the exhaust duct work for periodic inspection and cleaning.