Audio alarm. Change the alarm setting to on or off. The unit will emit an audible beep if there is a fault or if the unit changes to operate on battery, has a low battery condition, or is overloaded.
AUDIO ALARM: OFF
PRESS TO CHNG
Sensitivity. Select Low, Medium, or High to determine how often the until will switch to battery power. If the sensitivity it set to Low, the unit will tolerate more fluctuations in power, and will switch to battery less often. If the sensitivity is set to High, the unit will switch to battery power more often.
SENSITIVITY: MED
PRESS TO CHNG
Display dimmer. Change the brightness of the LCD display. Select Off for the display to completely darken when not in use. Push any button on the unit to illuminate the display.
DISPLAY DIM: ON
PRESS TO CHNG
Voltage transfer point. Set the value of the input utility voltage at which the unit will switch to battery power.
TO BAT IF < 88V
PRESS TO CHNG
Green function. Enable or disable the
GREEN FUNC: ON
PRESS TO CHNG
Green function - transfer threshold. Configure the master outlet to recognize when the master device has gone into sleep or standby mode. Configure the delay between when the Master unit turns off and the peripheral units turn off.
MASTER THRES: 25W
PRESS TO CHNG
CON ONDLY: 4 SEC
PRESS TO CHNG
CON OFFDLY: 4 SEC-
PRESS TO CHNG
Low battery warning. Set the time at which the unit will provide an audible warning that it almost exhausted battery power.
LOWBATTWARN: 2MIN
PRESS TO CHNG
APC A/V J Type Power Conditioner and Battery Backup | 7 |