Installing the XS400
DC Cables
For the best load starting performance, the DC cables should be as short and large as possible. See Table 
Table 2-1 Minimum Recommended DC Input Cable (copper) — AWG
| Cable Length: Battery to Inverter | Minimum Recommended | 
| (each cable) | Cable Size — AWG | 
| 
 | 
 | 
| No. 6 | |
| No. 4 | |
| No. 2 | |
| No. 0 | |
| 
 | 
 | 
DC Fuse and Disconnect or DC Circuit Breaker
If you are using a DC fuse and Disconnect, a maximum 80 amp Class T fuse shall be used for the DC fuse. A fuse of lower rating can be used, but it shall not be lower than 60 amp Class T. The Disconnect shall be rated at least 50 amps.
Alternately, a DC circuit breaker rated 50 amps can be used.