Trane DX1B060A9H31B, UX1C100A9H41B, UX1B080A9H31B, UX1B060A9H31B, UX1D120A9H51B manual Upflow Furnace

Page 17

 

 

 

 

 

 

Installer’s Guide

 

 

 

 

 

 

 

 

UPFLOW/ HORIZONTAL VENTING TABLE

 

 

 

 

 

 

 

TABLE 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MAXIMUM VENT LENGTH:

 

 

 

 

 

 

 

 

 

DIRECT VENT (2 PIPE SYSTEM) -

 

NONDIRECT VENT (1 PIPE SYSTEM) -

 

MAXIMUM TOTAL EQUIVALENT FEET FOR

MAXIMUM TOTAL EQUIVALENT FEET FOR

 

VENT AND INLET AIR PIPES (See Notes)

 

VENT PIPE ONLY (See Notes)

 

 

2" PIPE

2-1/2" PIPE

3" PIPE

4" PIPE

2" PIPE

2-1/2" PIPE

3" PIPE

4" PIPE

MODEL

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

*UX1B040A9H21B

60

80

100

130

50

 

80

80

130

*UX1B060A9H31B

60

80

100

130

50

 

80

80

130

*UX1B080A9H31B

50

80

100

130

40

 

80

80

130

*UX1C100A9H41B

NOT ALLOWED

40

100

130

NOT ALLOWED

40

80

130

*UX1D120A9H51B

NOT ALLOWED

40

100

130

NOT ALLOWED

40

80

130

 

 

 

 

 

 

 

 

 

 

NOTES: * - First letter may be "A" or "T"

1.The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot horizontal or vertical straight pipe section connected before or after the elbow.

2.DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).

If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.

3.MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes in two pipe systems).

4.One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.

5.The termination tee or bend must be included in the total number of elbows. If the BAYVENT100 termination kit is used, the equivalent length of pipe is 5 feet. There is zero equivalent length for the BAYVENT200.

6.Pipe adapters are field supplied.

7.4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.

MAXIMUM VENT LENGTH:

 

DIRECT VENT (2 PIPE SYSTEM) -

 

NONDIRECT VENT (1 PIPE SYSTEM) -

 

MAXIMUM TOTAL EQUIVALENT FEET FOR

MAXIMUM TOTAL EQUIVALENT FEET FOR

 

VENT AND INLET AIR PIPES (See Notes)

VENT PIPE ONLY (See Notes)

 

 

2" PIPE

2-1/2" PIPE

3" PIPE

4" PIPE

2" PIPE

2-1/2" PIPE

3" PIPE

4" PIPE

MODEL

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

& FITTINGS

*DX1B040A9H21B

60

80

100

130

50

80

80

130

 

 

 

 

 

 

 

 

 

*DX1B060A9H31B

50

80

100

130

50

80

80

130

 

 

 

 

 

 

 

 

 

*DX1B080A9H31B

45

80

100

130

40

80

80

130

 

 

 

 

 

 

 

 

 

*DX1C100A9H41B

NOT ALLOWED

80

100

130

NOT ALLOWED

80

80

130

*DX1D120A9H51B

NOT ALLOWED

15

60

130

NOT ALLOWED

25

70

130

NOTES: * - First letter may be "A" or "T"

1.The INLET AIR of one pipe systems require the installation of a 90° elbow (to prevent dust and debris from falling straight into thefurnace) and a 2 foot horizontal or vertical straight pipe section connected before or after the elbow.

2.DO NOT MIX PIPE DIAMETERS IN THE SAME LENGTH OF PIPE OUTSIDE THE FURNACE CABINET (Except adapters at the top of the furnace).

If different inlet and vent pipe sizes are used, the vent pipe must adhere to the maximum length limit shown in the table above (See Note 7 below for exception). The inlet pipe can be of a larger diameter, but never smaller than the vent pipe.

3.MAXIMUM PIPE LENGTHS MUST NOT BE EXCEEDED! THE LENGTH SHOWN IS NOT A COMBINED TOTAL, IT IS THE MAXIMUM LENGTH OF EACH (Vent or Inlet air pipes in two pipe systems).

4.One standard radius 90° elbow is equivalent to 12' of 4" pipe; one SHORT radius 90° elbow is equivalent to 10' of 3" pipe and one LONG radius elbow is equivalent to 6' of 3" pipe. One SHORT/LONG radius 90° elbow is equivalent to 7½' of 2½" pipe, & 5' of 2" pipe. Two 45° elbows equal one 90°elbow.

5.The termination tee or bend must be included in the total number of elbows. If the BAYAIR30VENTA termination kit is used, the equivalent length of pipe is 5 feet. There is zero equivalent length for the BAYVENT200.

6.Pipe adapters are field supplied.

7.4" pipe may be reduced to 3" for termination with BAYAIR30AVENTA or BAYVENT200 without additional length restriction.

d

UPFLOW FURNACE

B

Air Inlet

A

SINGLE PIPE VENTING Air Inlet

A (0-2') or greater

B (0-2') or greater

A+B = 2' minimum

A

Vent only to outside

DOWNFLOW

FURNACE

Vent only to outside

A = 2' minimum

18-CD22D1-8

17

Image 17
Contents Installer’s Guide Carbon Monoxide Poisoning Hazard Safety SectionInstaller’s Guide Contents Installer’s Guide UX1-H Outline DrawingDX1-H Downflow Installations Upflow InstallationHorizontal Installation Subbase Cross SectionOutside AIR is Recommended AIR for Combustion and VentilationConfined Space Return AIR Duct Systems Duct ConnectionsOptional Filter Rack Installation for BOT- TOM Return Typical Upflow Return AIR Filter InstallationsReturn AIR Filters Upflow Furnace onlyAirflow Typical Downflow Furnace Return AIR Filter Installations Alternate Upflow Filter Clip Bracket Installation KIT09224Models Cabinet Filter Numbers QTY & Size General Venting Bonding of PVC PVC Vent Fitting MaterialVent Fitting Material Plastic Vent and Inlet AIR Connections Horizontal VentingUpflow Furnace Inside Corner Detail Possible Configurations for TWO Pipe Venting Systems BAYVENT200B Horizontal Venting Through WallCombustible Material Wall Noncombustible Material WallBAYAIR30AVENTA BAYVENT200B Direction of Stainless Steel Fitting Downward VentingInstaller’s Guide EE Caution Used Through Chimney That Vents Another GAS ApplianceVertical Applications Condensate Drain InstructionsUpflow Vertical Horizontal ApplicationsDownflow Downflow VerticalVertical Downflow HorizontalTwinning Furnaces Electrical ConnectionsStage Heating only Thermostat Stage Heat / 1 Stage Cool Thermostat GAS PipingUpflow Left Hand GAS Piping Combustion and Input Check Orifice SizesHigh Altitude Derate Final Manifold Pressure SettingsPreliminary Inspections Start UP and AdjustmentReinstallation of the Burner BOX Cover Sequence of Operation Lighting InstructionsRoom AIR Thermostat Heat Anticipator Adjustment Airflow AdjustmentBurner BOX Temperature Limit Device Power FailureLimit switch must be reset by a qualified servicer Reset After Burner BOX Limit ShutdownIntegrated Furnace Control Error Flash Codes Trane