Trane DX1B080A9H31B, UX1C100A9H41B manual Possible Configurations for TWO Pipe Venting Systems

Page 19

 

 

 

 

Installer’s Guide

 

 

 

 

 

 

 

 

 

 

Non-Direct Vent Terminal Clearances

 

 

 

 

 

 

 

 

 

Canadian Installations

 

US Installations

 

 

 

 

 

A=

Clearance above grade, veranda, porch, deck, or

12 inches (30 cm)

 

12 inches (30 cm)

balcony

 

 

 

 

 

 

 

 

 

 

 

 

6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12

 

 

B=

Clearance to window or door that may be opened

inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<

 

4 feet (1.2m) below or to the side of opening; 1 foot (0.3m)

100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >

 

above opening.

 

 

 

 

 

100,000 Btuh (30 kw)

 

 

 

 

 

 

 

C=

Clearance to permanently closed window

*

 

*

 

 

 

 

 

 

Vertical clearance to ventilated soffit located above the

 

 

 

D=

terminal within a horizontal distance of 2 feet (61 cm)

*

 

*

 

from the center line of the terminal

 

 

 

 

 

 

 

 

E=

Clearance to unventilated soffit

*

 

*

 

 

 

 

 

F=

Clearance to outside corner

*

 

*

 

 

 

 

 

G=

Clearance to inside corner

*

 

*

 

 

 

 

 

H=

Clearance to each side of center line extended above

3 feet (91 cm) with a height 15 feet (4.5 m) above the

 

*

meter/regulator assembly

meter/regulator assembly

 

 

 

 

 

 

 

 

 

I=

Clearance to service regulator vent outlet

3 feet (91 cm)

 

*

 

 

 

 

 

 

 

6 inches (15 cm) for appliances =/< 10,000 Btuh (3 kw), 12

 

 

J=

Clearance to nonmechanical air supply inlet to building

inches (30 cm) for appliances > 10,000 Btuh (3 kw) and =/<

 

4 feet (1.2 m) below or to side of opening; 1 foot (300 m) above

or the combustion air inlet to any other appliance

100,000 Btuh (30 kw), 36 inches (91 cm) for appliances >

 

opening

 

 

 

 

100,000 Btuh (30 kw)

 

 

 

 

 

 

 

K=

Clearance to a mechanical air supply inlet

6 feet (1.83m)

 

3 feet (91 cm) above if within 10 feet (3m) horizontally

 

 

 

 

 

L=

Clearance above a paved sidewalk or paved driveway

7 feet (2.13 m) †

 

7 feet (2.13 m)

located on public property

 

 

 

 

 

 

 

 

 

 

M=

Clearance under veranda, porch, deck, or balcony

`12 inches (30 cm) ‡

 

*

 

 

 

 

 

Notes:

1.In accordance with the current CSA B149.1 Natural Gas and Propane Installation Code.

2.In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Code.

†.A vent shall not terminate directly above a sidewalk or paved driveway that is located between two single family dwelling and serves both dwellings.

‡. Pemitted only if veranda, porch, deck, or balcony is fully open on a minimum of two sides beneath the floor.

* Clearance in accordance with local installation codes and the requirements of the gas supplier and the manufacturer's Installation Instructions.

g

ELBOW AND TEE MUST BE

AS CLOSE TOGETHER

AS POSSIBLE

POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS

18-CD22D1-8

19

Image 19
Contents Installer’s Guide Carbon Monoxide Poisoning Hazard Safety SectionInstaller’s Guide Contents Installer’s Guide UX1-H Outline DrawingDX1-H Subbase Cross Section Upflow InstallationDownflow Installations Horizontal InstallationOutside AIR is Recommended AIR for Combustion and VentilationConfined Space Return AIR Duct Systems Duct ConnectionsUpflow Furnace only Typical Upflow Return AIR Filter InstallationsOptional Filter Rack Installation for BOT- TOM Return Return AIR FiltersAirflow QTY & Size Alternate Upflow Filter Clip Bracket Installation KIT09224Typical Downflow Furnace Return AIR Filter Installations Models Cabinet Filter NumbersGeneral Venting Vent Fitting Material Plastic PVC Vent Fitting MaterialBonding of PVC Vent and Inlet AIR Connections Horizontal VentingUpflow Furnace Inside Corner Detail Possible Configurations for TWO Pipe Venting Systems Noncombustible Material Wall Horizontal Venting Through WallBAYVENT200B Combustible Material WallBAYAIR30AVENTA BAYVENT200B Direction of Stainless Steel Fitting Downward VentingInstaller’s Guide EE Caution Used Through Chimney That Vents Another GAS ApplianceHorizontal Applications Condensate Drain InstructionsVertical Applications Upflow VerticalDownflow Horizontal Downflow VerticalDownflow VerticalTwinning Furnaces Electrical ConnectionsStage Heating only Thermostat Stage Heat / 1 Stage Cool Thermostat GAS PipingUpflow Left Hand GAS Piping Combustion and Input Check Orifice SizesHigh Altitude Derate Final Manifold Pressure SettingsReinstallation of the Burner BOX Cover Start UP and AdjustmentPreliminary Inspections Sequence of Operation Lighting InstructionsPower Failure Airflow AdjustmentRoom AIR Thermostat Heat Anticipator Adjustment Burner BOX Temperature Limit DeviceLimit switch must be reset by a qualified servicer Reset After Burner BOX Limit ShutdownIntegrated Furnace Control Error Flash Codes Trane