Baldor MN754 manual ‐1 Expansion Board Slot Locations

Page 12

3.Be sure drive operation is terminated and secured.

4.Remove all power sources from the control.

5.Wait at least 5 minutes for internal capacitors to discharge.

6.Refer to the control manual and remove the enclosure cover.

7.Open the control cover and locate Slots 1 & 2, see Figure 3‐1.

Note: Slot 3 is reserved for a feedback board only, encoder or resolver.

8.Install the expansion board in Slot 1 or 2. Be sure the board is securely pressed downward and makes good contact with the 48 pin connector in the slot position.

9.Secure the expansion board in the slot using the screw provided.

Figure 3‐1 Expansion Board Slot Locations

Installing board in Slot1

Installing board in Slot2

activates OP1 ANA 1 &

activates OP2 ANA 1 &

2 inputs & outputs.

2 inputs & outputs.

I/O Module

I/O Module

Slot1

Slot2

 

Feedback

 

Module Slot3

 

10.The mechanical installation of the expansion board is complete.

11.Refer to Jumper Definitions and configure the jumpers as desired.

12.Refer to Figures 3‐3 and 3‐4 and complete the wiring of the Analog Inputs and Outputs before you proceed to step 13.

13.When jumpers are set and connections are complete, close the control cover.

14.Refer to the control manual and close and secure the enclosure cover.

15.Restore all power sources to the control.

16.Restore drive operation.

3‐2 Installation

Image 12
Contents MN754 Page Table of Contents Ii Table of Contents Section General Information Introduction‐1 VS1 Expansion Boards Board Name Catalog No Limited Warranty Safety Notice ‐4 General Information Installation Considerations Section Expansion Board Description‐1 Characteristics ‐2 Signal ResolutionDigital Resolution Analog Resolution High Resolution Inputs High Resolution OutputsSection Installation Board InstallationReceiving & Inspection ‐1 Expansion Board Slot Locations Jumper Definitions Description‐3 High Resolution Input Connections Section Software Setup OverviewEXBHH005 HI RES Expansion Board Parameter Adjustable Range Factory User Setting Hi RES ParametersOpt1 Ana In1 Opt1 Ana In2 Opt2 Ana In1 Opt2 Ana In2 OP2 ANA IN1 Parameter Adjustable Range Factory User Set‐ Ting OP1 OP2 ANAOUT1 OP2 Level 2, Miscellaneous Block Section Troubleshooting Diagnostic ScreenInstalled Option Boards Display Comments‐2 Troubleshooting Baldor District Offices World Headquarters Box 2400 Fort Smith, AR